Configuration / parameterization
5.2 Parameterize
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
129
Device parameter
Default setting
Setting range
Response to current
limit violation
Warning
•
Warning
•
Trip
Lower current limit
18,75 %
•
18.75 to 100% of I
e
•
0% (= deactivated)
Increment: 3,125 %
Upper current limit
112,5 %
•
50 to 400% of I
e
•
0% (= deactivated)
Increment: 3,125 %
Blocking current
800 %
•
150 to 1000% von Ie
•
150 ... 800% of Ie
(sDS..., sRS...)
Increment: 50 %
Blocking time
1 s
1 to 5 s
Increment: 0.5 s
Response to
asymmetry
Trip
•
Warning
•
Trip
Asymmetry limit
30 %
30 ... 60% (0 = deactivated)
Increment: 10 %
Input signal extension 0 ms
0 to 200 ms
Increment: 10 ms
Input signal delay
10 ms
10 ... 80 ms
Increment: 10 ms
Input 1 level
Normally open
•
Normally closed
•
Normally open
Input 2 level
Input 3 level
Input 4 level
Input 1 action
No action
•
No action
•
Trip without restart
•
Trip with restart
•
Trip end position CW
•
Trip end position CCW
(RSte/sRSSte only)
•
Group warning
•
Manual operation local
•
Emergency start
•
Motor CW
•
Motor CCW (RSte/sRSSte only)
•
Quick stop
•
Trip reset
•
Cold run
Input 2 action
Input 3 action
Input 4 action
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......