Mounting / connection
4.2 Connection
M200D PROFIBUS/PROFINET
110
Manual, 08/2014, A5E01577426A/RS-AA/004
4.2.7
Inputs / outputs
Assignment of the digital inputs and outputs (M12 socket)
Pin
Input assignment
Output assignment
1
+ 24 V DC24V-NS (+)
N/C
2
N/C
N/C
3
0 V DC24V-NS (-)
0 V DC24V-S (-)
4
DIx
OUTx
5
FE
FE
4.2.7.1
Digital inputs IN1 to IN4
The motor starters are equipped with four digital inputs, which you can connect directly to
sensors (PNP) (2 and 3-wire system).
Connectors (M12, 5-pin, A-coded) are used for this purpose. The motor starter is equipped
with a range of sockets.
Note
Short-circuit hazard
Do not use an external power supply since this can result in a short-circuit.
Pin assignment
The following diagrams show examples of circuits (2 and 3-wire system):
2-wire system
3-wire system
Note
The supply voltage for the digital inputs is short-circuit proof. The current is limited to max.
200 mA. If a short-circuit or overload situation occurs in the sensor supply, the switching
element (motor) and brake output are shut down and a group fault is output. You must
acknowledge this fault with a trip reset.
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......