Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
206
Manual, 08/2014, A5E01577426A/RS-AA/004
A.1.13
DS95 Read statistics
Object
No.
Byte.Bit Meaning
Value range/[encoding]
Increment Relevant for
607
0
Motor current I
max
0 ... 797 %
3.125 %
All
—
1
Reserved
—
—
—
606
2 ... 3
Last trip current
0 ... 1 000 % / [unsigned 16]
3.125 %
All
602
4 ... 7
Operating hours device
0 ... 16777215 / [unsigned 32]
1 min
All
1)
603
8 ... 11
Number of starts motor CW
0 ... 16777215 / [unsigned 32]
1
All
604
12 ... 15 Number of starts motor CCW
0 ... 16777215 / [unsigned 32]
1
.RS... only
605
16 ... 17 Number of overload trips
0 ... 65535 / [unsigned 16]
1
All
609
20 ... 23 Motor current I
max (rms)
0 ... 20000 A / [signed 32]
0.01 A
All
608
24 ... 27 Last tripping current I
A(rms)
0 ... 20000 A / [signed 32]
0.01 A
All
602
28 ... 31 Operating hours motor
0 ... 4 294 967 295 / [unsigned 32]
1 s / 1 min
All
611
32 ... 35 Operating hours motor current
= 18 to 49.9% of I
emax
0 ... 4 294 967 295 / [unsigned 32]
1 s / 1 min
All
1)
612
36 ... 39 Operating hours motor current
= 50 to 89.9% of I
emax
0 ... 4 294 967 295 / [unsigned 32]
1 s / 1 min
All
1)
613
40 ... 43 Operating hours motor current
= 90 to 119.9 % of I
emax
0 ... 4 294 967 295 / [unsigned 32]
1 s / 1 min
All
1)
614
44 ... 47 Operating hours motor current
= 120 to 1000% of I
emax
0 ... 4 294 967 295 / [unsigned 32]
1 s / 1 min
All
1)
616
50 ... 51 Number of switching element
overload trips
0 ... 65535 / [unsigned 16]
1
All
618
54 ... 55 Number of short-circuit trips
0 ... 65535 / [unsigned 16]
1
All
619
56 ... 59 Number of stops with mechanical
braking
0 ... 4 294 967 295 / [unsigned 32]
1
All with BO
2)
621
64-67
Number of starts output 1
0 ... 4 294 967 295 / [unsigned 32]
1
All
622
68-71
Number of starts output 2
0 ... 4 294 967 295 / [unsigned 32]
1
All
625
80-83
Number of starts output BO
0 ... 4 294 967 295 / [unsigned 32]
1
All with BO
2)
626
84-87
Maintenance timer
0 ... 4 294 967 295 / [unsigned 32]
1 s
All
1)
Special feature of operating hours
The motor starter records 2 operating hour values:
The operating hours of the motor indicate how long the switching elements and thus the motor were switched on.
The operating hours of the device (motor starter) indicate how long the power supply 24 V-NS DC of the motor starter was
switched on.
Both operating hour values are recorded in data set 95 - Read statistics. They are entered in the data field "Operating
hours" alternately at 5-second intervals. The bit "Operating hours selection" specifies which of the two operating hours
values has been transferred.
[0]: Operating hours motor
[1]: Operating hours - device.
The operating hours are recorded in the range from 0 to 16,777,215 minutes in 1-second steps.
2)
BO: Brake output
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......