Functions
3.7 System monitoring
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
55
Input n action
Different actions can be triggered when an input signal is present. You can parameterze the
following actions dependent on "Input n level", "Input n signal" and "Mode".
Note
If "Input n signal" = retentive and "Input n action" = Motor CW/CCW, at least one input must
always be parameterized with input action "Tripping ... " or "Quick Stop".
If this rule is violated, the motor starter will reject the parameters with the relevant
diagnostics message!
Input n action
Level
Signal
Mode
Description
No action
NO/NC
n-ret./ret. All
-
Trip without restart
NO/NC
n.ret./-
All
•
Causes the motor and brake to trip.
•
Must be acknowledged once the cause of the tripping
has been rectified (initial status).
Trip with restart (auto
reset)
NO/NC
n.ret./-
All
•
Causes the motor and brake to trip.
•
Acknowledged automatically once the cause of the
tripping has been rectified (initial status).
Trip end position CW
NO/NC
n.ret./-
All
•
The motor and the brake output are tripped
regardless of the direction of rotation.
•
The brake output can be switched on again once the
"Brake" and "Motor CW / CCW" control commands
have been canceled.
•
Trip end position CW rotation: The motor can only be
switched on again with the opposite command
("Motor CCW").
•
Trip end position CCW The motor can only be
switched on again with the opposite command
("Motor CW").
Trip end position CCW
(RSte/sRSSte only)
NO/NC
n.ret./-
All
Group warning
NO/NC
n-ret./ret. All
•
The "Group warning" message is set.
•
The motor starter and the brake output are not
tripped!
ret.:
The input action responds to the active edge of the
input signal. Deactivation with a pending active input
signal is thus possible.
Action is deactivated with trip reset.
Manual mode local
NO/NC
n.ret./-
All
•
Control is only possible via "input n action": "Motor
CW" and "Motor CCW" (see below) possible!
•
Control is not possible over the fieldbus ("Automatic"
mode)!
•
"Automatic" mode is only possible again if manual
mode local is canceled and "Input n action": "Motor
CW" or "Motor CCW" is not active.
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......