Mounting / connection
4.2 Connection
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
103
4.2.2
Required components/cables
Selecting the power cables
DANGER
Hazardous Voltage
Can Cause Death, Serious Injury, or Property Damage
Before starting work, disconnect the system and devices from the power supply.
The cross-section of the power cables must be suitable for the prevailing ambient conditions.
The following factors determine the cross-section:
●
The current set on the device
●
The cable installation type
●
The ambient temperature
●
The type of material (PVC, rubber)
The following maximum current-carrying capacities apply for PVC power cables when
installed, for example, in the cable duct (depending on the ambient temperature):
Cross-section T
U
= 30 °C
T
U
= 40 °C
T
U
= 45 °C
T
U
= 50 °C
T
U
= 55 °C
1.5 mm
2
14 A
12.2 A
11.1 A
9.9 A
8.5 A
2.5 mm
2
19 A
16.5 A
15.0 A
13.5 A
11.6 A
4.0 mm
2
26 A
22.6 A
20.5 A
18.5 A
15.9 A
6.0 mm
2
33 A
28.7 A
26.1 A
23.4 A
18.2 A
Unused connections
Note
Unused connections
Seal unused connections with sealing caps since this is the only way to ensure degree of
protection IP65. The sealing caps of the digital inputs and outputs are mounted on the motor
starter module as delivered.
The sealing caps are also available as accessories:
Item
Number
Order number
Sealing cap M12
10 pieces
3RK1901-1KA00
Sealing cap 7/8"
10 pieces
6ES7194-3JA00-0AA0
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......