A.1.16
DS131 Read/write device parameters
Complete data sets can be exchanged with the starters during operation via the acyclic
channel (PROFIBUS) and the NRT channel (PROFINET).
We recommend initially reading out data set 131 from the motor starter with the current
parameters, changing the corresponding parameters and then rewriting these to the motor
starter.
Please be aware that the coordination (Byte 0) is to be set to 0x21 prior to writing the data
set.
The following elements of data set 131 (138 bytes) are used to parameterize the M200D
PROFIBUS/PROFINET motor starters.
Object
No.
Byte.Bit
Parameters / content
Range of values
Increment
Default
setting
Relevant for
Preamble
—
0
Coordination
0x21 Write via acyclic bus channel (PLC)
—
1
Reserved
0x00
—
2
Reserved
0x00
—
3
Reserved
0x00
Device parameter
120
4 ... 7
Device functions_2
MLFB-specific content,
see table 'Device functions' in connection with data set 131
1
8 ... 11
Device functions_1
130
14.0 ... 7
and
15.0 to 7
Rated operating current
I
e
A
0.15 ... 2.0 A
1.5 ... 12 A
10 mA
0.15 / 2.0
1.5 / 12.0
All starters
3
16.0
Load type
[0] 3-phase motor
[1] 1-phase motor
—
[0]
DSte / RSte
4
16.1
Protection against
voltage failure
[0] No
[1] Yes
—
[1]
All starters
136
17.0 ... 7 Prewarning limit – motor
heating
0 ... 95 %;
[0] = deactivated
5 %
[0]
All starters
5
18.0 ... 1 Response to overload
Thermal motor model
[0] Tripping without restart
[1] Tripping with restart
[2] Warning
—
[0]
All starters
6
19.0 ... 3 Trip class
(2 A, 12 A)
[0] CLASS 10
[1] CLASS 20
[3] CLASS 5 (10a)
[4] CLASS 15
[15] CLASS OFF
5 (10a),
10,
15,
20,
CLASS OFF
[0]
All starters
7
20.0 ... 7 Recovery time
1 min … 30 min
0.5 min
1.5 min
All starters
8
21.0 ... 7 Idle time
0 s to 255 s ; 0 = deactivated
1 s
0
All starters
137
22 ... 23
Prewarning limit –
remaining time for
tripping
0 s to 500 s;
0 = deactivated
1 s
0 s
All starters
10
24.0 ... 1 Response to overload
temperature sensor
[0] Tripping without restart
[1] Tripping with restart
[2] Warning
—
[0]
All starters
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......