Functions
3.21 PROFIenergy
M200D PROFIBUS/PROFINET
86
Manual, 08/2014, A5E01577426A/RS-AA/004
t
off
Time_to_Pause
Time the starter requires in order to change to power saving
mode. This time is always 100 ms for M200D. A
parameterized running down time is added to this in the
case of a soft starter (if available and if the starter was in the
ON state):
t
off
= 100 ms + running down time
If the soft starter was already off before the pause, pause
mode will be switched to after 100 ms only.
t
off_min
Time_min_length_of_stay
Minimum time that the device spends or should spend in
saving mode.
For M200D: 0 ms
t
on
Time_to_operate
Time that will elapse before the starter changes back to the
operating state. Since the process image is evaluated again
immediately when the M200D exits power saving mode, this
time is 0 ms.
t
Pause_min
Time_min_Pause
Time that is compared with t
Pause
(is transferred together
with the "Start_Pause" command to the motor starter);
if t
Pause
≥ t
Pause_min
, the device switches to saving mode.
Содержание SIRIUS M200D
Страница 2: ......
Страница 16: ...Product description 1 3 PROFIenergy M200D PROFIBUS PROFINET 16 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 24: ...Product family 2 3 Design concept M200D PROFIBUS PROFINET 24 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 90: ...Functions 3 22 Logbook M200D PROFIBUS PROFINET 90 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 118: ...Mounting connection 4 2 Connection M200D PROFIBUS PROFINET 118 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 222: ...Appendix A 2 Order numbers M200D PROFIBUS PROFINET 222 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 224: ...Correction sheet M200D PROFIBUS PROFINET 224 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 232: ...Index M200D PROFIBUS PROFINET 232 Manual 08 2014 A5E01577426A RS AA 004 ...
Страница 233: ......