2 Functions
66
7ST6 Manual
E50417-G1176-C251-A3
mally set to at least 120 % of the line length. The delay times are set in accordance
with the type of application, usually to zero or a very small delay.
Furthermore, these zones do not have alternative parameters for the reach and the
minimum load impedance (see Table 2-3).
Overreach Zone,
Manual Close
If the circuit breaker is manually closed onto a short circuit, the distance protection can
issue an instantaneous trip command.
The parameter
SOTF zone
(address
1232
) can be used to determine the zone(s) for
which instantaneous tripping following manual closing applies. With the setting
SOTF
zone
=
PICKUP
, tripping occurs with the zones described above. When the protection
trips on closing onto a fault, the indication
„Dis TRIP PU MC“
is output. With the
setting
SOTF zone
=
Overreach Zone
the ZOR zone is temporarily enabled.
The overreach zone ZOR is a zone which can be activated for a settable time
SI
Time Man.Cl
in case of a manual closure. This setting of the parameter
SI Time
Man.Cl
(address
1150
) is only possible with DIGSI® under
Additional Settings
(see
Subsection 2.1.5.1). This zone is provided for protection of the entire line by instanta-
neous tripping. It has therefore the same settings as zone Z1B.
The following parameters can be set for the dependent zones:
Table 2-3
Assignment of setting parameters for the dependent zones of the distance pro-
tection
The setting parameters marked with „reverse“ (e.g. Z1B reverse) are only visible if you
have set „
non-directional
“ for the distance stage of the corresponding zone.
Dependent
Zone
Parameter
Setting Parameter Forwards
Setting Parameter Reverse
Zone Z1B
Z
Z1B (Addr.1325)
X1B (Addr.1324)
Z1B Reverse (Addr.1328)
X1B Reverse (Addr.1327)
R
L
R1B (Addr.1323)
R1B Reverse (Addr.1326)
Mode
Op. Mode Z1B (Addr.1321)
Zone Z1L
Z
Z1L (Addr.1335)
X1L (Addr.1334)
Z1L Reverse (Addr. 1338)
X1L Reverse (Addr. 1337)
R
L
R1L (Addr.1333)
R1L Reverse (Addr.1336)
Mode
Op. Mode Z1L (Addr.1331)
Overreach
Zone
Z
ZOR (Addr.1384)
XOR (Addr.1383)
ZOR Reverse (Addr.1390)
XOR Reverse (Addr.1389)
R
L
ROR (Addr.1382)
ROR Reverse (Addr.1388)
Mode
Op. Mode ZOR (Addr.1381)
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7ST6
Страница 14: ...Contents 14 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 24: ...1 Introduction 24 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 254: ...3 Mounting and Commissioning 254 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 288: ...4 Technical Data 288 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 340: ...A Appendix 340 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 342: ...Literature 342 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 354: ...Index 354 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 355: ...Index 355 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 356: ...Index 356 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...