1.3 Characteristics
23
7ST6 Manual
E50417-G1176-C251-A3
Trip Circuit Super-
vision
• Integrated trip circuit supervision
User Defined
Functions
(optional)
• Freely programmable combination of internal and external signals for the imple-
mentation of user-defined logic functions
• All common logic functions
• Delays and limit-value inquiries
Breaker Control
• Switchgear can be activated and de-activated manually via local control keys
(7ST63), the programmable function keys, via the system interface (e.g. SITRAS
®
SCS), or via the operating interface (using a personal computer and the DIGSI
®
software);
• Feedback on switching states via the circuit breaker auxiliary contacts (for com-
mands with feedback)
• Plausibility monitoring of the circuit breaker positions and interlocking conditions for
switching.
Monitoring
Functions
• Availability of the device is greatly increased because of self-monitoring of the inter-
nal measurement circuits, power supply, hardware, and software
• Monitoring of overhead contact line voltage (Fuse Failure Monitoring);
• Monitoring of ambient temperature sensing
• Trip circuit supervision possible;
• Display of operating impedances and direction
Further Functions
• Battery buffered real time clock, which may be synchronized via a synchronization
signal (e.g. DCF77, IRIG B via satellite receiver), binary input or system interface
• Continuous calculation and display of measured quantities on the front display
• Fault event memory (trip log) for the last 8 network faults (faults in the power sys-
tem), with real time stamps
• Fault recording and data transfer for fault recording for a maximum time range of
15 s
• Statistics: Counter with the trip commands issued by the device, as well as record-
ing of the current-time integrals, the fault current data and accumulation of the in-
terrupted fault currents
• Communication with control center possible via serial interfaces (depending on the
ordering variant), optionally via data line, modem or fibre optics;
• Commissioning aids such as connection and direction checks as well as circuit
breaker test functions
■
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7ST6
Страница 14: ...Contents 14 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 24: ...1 Introduction 24 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 254: ...3 Mounting and Commissioning 254 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 288: ...4 Technical Data 288 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 340: ...A Appendix 340 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 342: ...Literature 342 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 354: ...Index 354 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 355: ...Index 355 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 356: ...Index 356 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...