A Appendix
320
7ST6 Manual
E50417-G1176-C251-A3
3901
FCT BreakerFail
Breaker Failure
ON
OFF
OFF
Breaker Failure Protection is
3902
I> BF
Breaker Failure
1A
0.05 .. 20.00 A
0.10 A
Pick-up threshold I>
5A
0.25 .. 100.00 A
0.50 A
3904
tBF1
Breaker Failure
0.10 .. 10.00 sec;
∞
0.50 sec
Delay Time Backup Trip Element
3905
tBF2
Breaker Failure
0.10 .. 10.00 sec;
∞
0.75 sec
Delay Time Higher-Level Protec-
tion
4001
FCT TripSuperv.
TripCirc.Superv
ON
OFF
OFF
TRIP Circuit Supervision is
4002
No. of BI
TripCirc.Superv
1 .. 2
2
Number of Binary Inputs per trip
circuit
4003
Alarm Delay
TripCirc.Superv
1 .. 30 sec
2 sec
Delay Time for alarm
4101
It FUNCTION
It Function
ON
OFF
ON
It Function
4102
T00
It Function
0.001 .. 0.100 sec; 0
0.005 sec
CB Response Time
4103
DELTA AuxCont
It Function
-0.050 .. 0.050 sec
0.000 sec
Time Diff. CB Main and Auxiliary
Contact
4104
It ALARM
It Function
1.0 .. 1000.0 ;
∞
500.0
Alarm Stage of It Detection in
I/In*s
4201
Ther. OVER LOAD
Therm. Overload
OFF
ON
OFF
Thermal overload protection
4202
CAT CHANGEOVER
Therm. Overload
Binary Input
Protocol
Setting
Blocked
Binary Input
Catenary Changeover
4203
TAU
Therm. Overload
2.0 .. 30.0 min
5.0 min
Thermal Time Constant
4204
k ITRise
Therm. Overload
0.10 .. 4.00
1.20
Max. Permissible Current Factor
ITRise
4205
T Rise
Therm. Overload
0 .. 100 K; < > 0
50 K
Final Temperature at ITRise
4206
TEMP TRIP
Therm. Overload
50 .. 100
°
C
50
°
C
Tripping Temperature
4207
TEMP ALARM
Therm. Overload
40 .. 100
°
C
40
°
C
Alarm Temperature
4208
TEMP CLOSE
Therm. Overload
25 .. 100
°
C
40
°
C
Closing Temperature
4210
CHANGE TO CAT
Therm. Overload
CAT1 active
CAT2 active
CAT3 active
CAT1 active
Change to Catenary
4211
CAT2
Therm. Overload
1.0 .. 3.0
1.0
Factor for 2 Catenaries
4212
CAT3
Therm. Overload
1.0 .. 3.0
1.0
Factor for 3 Catenaries
4215
AMB.TEMP.
Therm. Overload
-55 .. 40
°
C
15
°
C
Ambient Temperature Value
4216
MIN TEMP PRESET
Therm. Overload
-55 .. 40
°
C
-55
°
C
Minimum Setting Ambient Tem-
perature
4301
Defrosting
Defrosting
ON
OFF
OFF
Defrosting Protection
4302
ID>
Defrosting
0.10 .. 2.00 I/In
0.40 I/In
Pickup Current ID> Defrosting
Protection
4303
T ID>
Defrosting
0.00 .. 30.00 sec;
∞
0.10 sec
Delay Time ID> for Defrosting
Protection
4304
k
Defrosting
0.00 .. 0.80
0.50
Charact. Slope of Defrosting Pro-
tection
4306
IX>>
Defrosting
1A
0.10 .. 25.00 A;
∞
2.00 A
Pickup Current High-Set Stage
IX>>
5A
0.50 .. 125.00 A;
∞
10.00 A
4307
T IX>>
Defrosting
0.00 .. 30.00 sec;
∞
0.30 sec
Delay Time IX>>
4308
IX>
Defrosting
1A
0.10 .. 25.00 A;
∞
1.50 A
Pickup Overcurrent Stage IX>
5A
0.50 .. 125.00 A;
∞
7.50 A
4309
T IX>
Defrosting
0.00 .. 30.00 sec;
∞
0.50 sec
Delay Time IX>
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7ST6
Страница 14: ...Contents 14 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 24: ...1 Introduction 24 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 254: ...3 Mounting and Commissioning 254 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 288: ...4 Technical Data 288 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 340: ...A Appendix 340 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 342: ...Literature 342 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 354: ...Index 354 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 355: ...Index 355 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 356: ...Index 356 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...