2 Functions
148
7ST6 Manual
E50417-G1176-C251-A3
Address
3530
Op.mode with MC
determines whether closing under asynchronous
system conditions is allowed for manual closing or reclosure via control command. Set
this parameter to
with T-CB close
to allow asynchronous closing; the relay will
then consider the circuit breaker closing time before determining the correct instant for
the close command. Remember that closing under asynchronous system conditions
is allowed only if the circuit breaker closing time is set correctly (see above under „Pre-
conditions“)! If you wish to permit manual closure or closing via control command only
under synchronous system conditions, set this address to
w/o T-CB close
.
The permissible magnitude difference of the voltages is set in address
3531
MC
maxVolt.Diff
. The setting is applied in Volts secondary. This value can be entered
as a primary value when parameterizing with a PC and DIGSI
®
.
The permissible frequency difference between the voltages is set in address
3532
MC
maxFreq.Diff
, the permissible phase angle difference in address
3533
MC
maxAngleDiff
.
The further release conditions for manual reclosing or reclosure via control command
are set in addresses
3535
to
3539
.
The following addresses mean:
3535
MC SYNCHR
the busbar (URef) and the feeder (ULine) must both be
live (
Live Volt. Thr.
, address
3503
); the condi-
tions for synchronism are checked, i.e.
MC
maxVolt.Diff
(address
3531
),
MC maxFreq.Diff
(address
3532
) and
MC maxAngleDiff
(address
3533
). This parameter can only be altered with DIGSI
®
under
Additional Settings
.
3536
MC Uref>Uline<
The busbar (URef) must be live (
Live Volt. Thr.
,
address
3503
), the feeder (ULine) must be dead
(
Dead Volt. Thr.
, address
3502
);
3537
MC Uref<Uline>
The busbar (URef) must be dead (
Dead Volt. Thr.
,
address
3502
), the feeder (ULine) must be live (
Live
Volt. Thr.
, address
3503
);
3538
MC Uref<Uline<
The busbar (UBus) and the feeder (ULine) must both
be dead (
Dead Volt. Thr.
, address
3502
);
3539
MC O/RIDE
Manual closing or closing via control command is re-
leased without any check.
The five possible release conditions are independent of each other and can be com-
bined.
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7ST6
Страница 14: ...Contents 14 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 24: ...1 Introduction 24 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 254: ...3 Mounting and Commissioning 254 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 288: ...4 Technical Data 288 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 340: ...A Appendix 340 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 342: ...Literature 342 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 354: ...Index 354 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 355: ...Index 355 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 356: ...Index 356 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...