2 Functions
78
7ST6 Manual
E50417-G1176-C251-A3
Definite Time High-
set Current Stage
I>>
The logic of the high-set current stage I>> is the same as that of the I>>> stage. The
two stages differ only in their parameters for the current threshold and the delay time.
The parameter
I>>
is used for the current threshold, and the parameter
T I>>
for the
delay time. In all other respects Figure 2-14 applies.
Definite Time Over-
current Stage I>
This stage is available if the parameter
CURVE O/C
is set to
Definite Time
. By
default this stage is available. The logic of the time overcurrent stage I> is the same
as that of the I>> stage. The parameter
I>
is used for the current threshold, and the
parameter
T I>
for the delay time. In all other respects Figure 2-14 applies.
Inverse-Time Over-
current Stage Ip
The inverse-time overcurrent stage is available if the parameter
CURVE O/C
is set to
TOC ANSI
or
TOC IEC
. This parameter is also used to make a preselection of the
characteristics available in the inverse-time overcurrent stage. This stage differs from
the definite-time overcurrent stage I> by its current-dependent delay time characteris-
tic. The delay time of the stage is the delay time associated with the applied current in
the selected characteristic. Selectable characteristics are shown in the Technical Data
in Section 4.3. The pickup current is set in the parameter
IP
. The delay time of the
characteristic is calculated with the multiplier set in the parameter
T IP
or
D IP
.
Like all other stages, the inverse-time overcurrent stage has a logic for switching onto
fault and can be blocked by the inrush restraint feature. A blocking signal generates
the indication
„O/C Rush blk“
.
The following figure shows the logic diagram. In the configuration notes (Subsection
2.3.2) the different setting addresses are elaborated upon.
Figure 2-15
Pick-up and tripping logic of the inverse time overcurrent stages
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7ST6
Страница 14: ...Contents 14 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 24: ...1 Introduction 24 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 254: ...3 Mounting and Commissioning 254 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 288: ...4 Technical Data 288 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 340: ...A Appendix 340 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 342: ...Literature 342 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 354: ...Index 354 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 355: ...Index 355 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 356: ...Index 356 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...