2 Functions
40
7ST6 Manual
E50417-G1176-C251-A3
2.1.5
Power System Data 2
The general protection data (
P.System Data 2
) include settings associated with all
functions rather than a specific protection, monitoring or control function. In contrast
to the
P.System Data 1
as discussed before, these can be changed over with the
setting groups and can be configured via the operator panel of the device.
2.1.5.1
Setting Notes
System Data
The parameters of System Data are only accessible if address
138
Fault Locator
has been set to
Enabled
in the functional scope.
Depending on the settings under
P.System Data 1
, you set the reactance per unit
length characteristics for up to 5 line sections in the
P.System Data 2
under . These
values are needed for conversion of the fault impedance into a fault distance.
The reactance per unit length characteristic X´ is entered as a secondary value. At
address
1110
X1
you set the secondary reactance per unit length characteristic for
the 1st line section in
Ω
/km if the unit length set under System Data is
km
(address
236
, see Subsection 2.1.3.1).
At address
1111
d1
you set the corresponding line length of the 1st line section. The
device needs these values for conversion of the fault impedance into a fault distance.
At address
1160
X1
you set the secondary reactance per unit length characteristic for
the 1st line section in
Ω
/mile if the unit length set under System Data is
Miles
(ad-
dress
236
, see Subsection 2.1.3.1).
At address
1161
d1
you set the corresponding line length of the 1st line section. The
device needs these values for conversion of the fault impedance into a fault distance.
Manual Close
At address
1150
SI Time Man.Cl
you set the action time (seal-in time) for the
manual close signal. The parameter
SI Time Man.Cl
can only be altered with
DIGSI® under Additional Settings.
At address
1151
SYN.MAN.CL
you specify whether a synchro-check (
with Sync-
check
) will be performed in case of a manual closure or not (
w/o Sync-check
).
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7ST6
Страница 14: ...Contents 14 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 24: ...1 Introduction 24 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 254: ...3 Mounting and Commissioning 254 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 288: ...4 Technical Data 288 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 340: ...A Appendix 340 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 342: ...Literature 342 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 354: ...Index 354 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 355: ...Index 355 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 356: ...Index 356 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...