!PPENDIX
3*
6
# ' #
2935 LIMITcosphi<
Limit of power factor
min. 0.40
max. 1.00
¬¬¬¬
2936 LIMIT Pa
Limit of active power
min. 1
kW
max. 500000
¬¬¬¬
2937 LIMIT Pr
Limit of reactive power
min. 1
kVAR
max. 500000
¬¬¬¬
¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
3000 EARTHFAULT DETECTION
3001 EARTHFAULT
High-sensitivity earth fault protection
OFF
[ ] off
ON
[ ] on
ALARM ONLY
[ ] Alarm only
3002 CT ERR. I1
Second. current I1 for max error angle of C.T.
min. 0.003
A
max. 1.600
¬¬¬¬
3003 CT ERR. F1
Error angle of C.T. at I1
min. 0.0
à
max. 5.0
¬¬¬¬
3004 CT ERR. I2
Second. current I2 for max error angle of C.T.
min. 0.003
A
max. 1.600
¬¬¬¬
3005 CT ERR. F2
Error angle of C.T. at I2
min. 0.0
à
max. 5.0
¬¬¬¬
3006 Uph<
Phase-earth voltage of faulted phase Uph<
min. 10
V
max. 100
¬¬¬¬
3007 Uph>
Phase-earth voltage of healthy phases Uph>
min. 10
V
max. 100
¬¬¬¬
3009 Ue> meas.
Pick-up level of measured UE
min. 1.8
V
max. 130.0
¬¬¬¬
3010 Ue> cal.
Pick-up level of calculated UE
min. 6.0
V
max. 130.0
¬¬¬¬
3011 T-E/F
Duration of displacement voltage for E/F det.
min. 0.04
s
max. 320.00/Ô
¬¬¬¬
3012 T-UE
Delay time T-UE of the UE> stage
min. 0.10
s
max. 40000.00/Ô ¬¬¬¬