!PPENDIX
3*
6
# ' #
1219 CHARACTER.
Characteristic of the O/C stage Ip
INVERSE
[ ] Inverse
SHORT INVERSE
[ ] Short inverse
LONG INVERSE
[ ] Long inverse
MODERATELY INV. [ ] Moderately inverse
VERY INVERSE
[ ] Very inverse
EXTREMELY INV.
[ ] Extremely inverse
DEFINITE INV.
[ ] Definite inverse
I-SQUARED-T
[ ] I-squared-t
1221 MAN.CLOSE
Manual close
I>> UNDELAYED
[ ] I>> undelayed
I>/Ip UNDELAYED [ ] I>/Ip undelayed
INEFFECTIVE
[ ] Ineffective
1223 RAR st. ph
RAR stage phase
I>> ALWAYS
[ ] I>> always active
I>> W. RAR ONLY [ ] I>> with RAR only
1230 USER DEF. CHARACTERISTIC
User def. characteristic, O/C stage Ip
¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
1300 O/C PROT. EARTH
1301 O/C EARTH
O/C protection for earth faults
ON
[ ] on
OFF
[ ] off
1302 IE>>
Pick-up value of the high-set stage IE>>
min. 0.05
I/In
max. 25.00
¬¬¬¬
1303 T-IE>>
Trip time delay of the high-set stage IE>>
min. 0.00
s
max. 60.00/Ô
¬¬¬¬
1306 MEAS.REPET
Measurement repetition
NO
[ ] no
YES
[ ] yes
1312 IE>
Pick-up value of the overcurrent stage IE>
min. 0.05
I/In
max. 25.00/Ô
¬¬¬¬
1313 T-IE>
Trip time delay of the overcurrent stage IE>
min. 0.00
s
max. 60.00/Ô
¬¬¬¬
1314 IEp
Pick-up value inverse time O/C stage IEp
min. 0.05
I/In
max. 4.00/Ô
¬¬¬¬
1315 T-IEp
Trip time delay inverse time O/C stage IEp
min. 0.05
s
max. 3.20/Ô
¬¬¬¬
1316 D IEp
Trip time delay inverse time O/C stage IEp
min. 0.50
max. 15.00/Ô
¬¬¬¬
www
. ElectricalPartManuals