Introduction

 

 
 
This operating instruction shall familiarize you with the

 

safety relay controller 

models: PRSU/2, PRSU/4 and PRSU/5. 

 

Target Audience

 

These operating instructions are addressed to the following personnel: 
 

 

Skilled personnel who plan or develop safety equipment for machines 
and plants, who are familiar with the safety instructions and safety 

 

regulations.

 

 

 

Skilled personnel who build, install, maintain and operate safety 

 

equipment in plants and machinery.

 

Symbol Key 
 

These operating instructions contain several symbols which are used to  
highlight important information: 
 
 

 

This symbol indicates text passages which 

must absolutely be paid attention 

to.

 Disregarding may lead to serious personal injury or damage to property. 

 

 

 
This symbol indicates text passages which contain important information. 
 

 

 
This sign is used to indicate actions by the installer or operator. 
 
 

 

This sign illustrates that a condition has changed after an action has been 
carried out. 
 
 

 

 

 

PRSU/2, PRSU/4, PRSU/5 

 

Operating Instructions Manual 

 

Safety controllers for safety mats and  

sensing edge products 

Содержание PRSU/2

Страница 1: ...lants who are familiar with the safety instructions and safety regulations Skilled personnel who build install maintain and operate safety equipment in plants and machinery Symbol Key These operating...

Страница 2: ...regulations for safety at work and accident prevention and who have read this manual s content in full Installation assembly and maintenance of electrical equipment is only permitted by specialized s...

Страница 3: ...voltage of 24VDC or 24VAC This model features two normally open safety relays that are triggered by the Sensor Monitoring terminals S11 S12 S21 S22 Terminals Description A1 Power input 24VDC or 24VAC...

Страница 4: ...relays that are triggered by the Sensor Monitoring terminals S11 S12 S21 S22 This model also features an additional normally closed auxiliary relay not for safety use Terminals Description A1 Power in...

Страница 5: ...ty relays that are triggered by the Sensor Monitoring terminals S11 S12 S21 S22 This model also features an additional normally closed auxiliary relay not for safety use Terminals Description A1 Power...

Страница 6: ...or more information After the RESET signal is received and the monitored switch is in the unactuated state the relay contacts 13 14 23 24 will close Device Startup Verification PRSU 4 PRSU 5 Before cr...

Страница 7: ...application will require only a single PRSU 2 PRSU 4 or PRSU 5 the following rule of thumb guidelines can be used Recommended Application Limits Product Type Maximum Area Maximum Length ControlMat Arm...

Страница 8: ...ch on the rear of the unit for DIN Rail attachment Electrical Connections Wire the device based on which of the following options best suits the target application RESET Mode Control Wiring 1 Automati...

Страница 9: ...closure is broken and a RESET signal is manually generated by the operator via a mechanical N O pushbutton or switch 3 Conditional In this operating mode the RESET signal cannot propagate unless all o...

Страница 10: ...nergize Warning For this configuration to work as intended the series resistance between each end of the sensor s conductors cannot exceed 10 Additionally the short circuit resistance between both of...

Страница 11: ...no terminal of the device is connected to a live voltage before continuing 2 Unscrew terminals A1 and A2 from the device before removing any other connections 3 One at a time free connections from the...

Страница 12: ...es In cases where either one or both Channel LEDs is OFF during normal operation please verify that the device is properly wired If the problem persists the device is no longer capable of service Reti...

Страница 13: ...47 5 1 AC 15 3 A DC 13 3 A Max Switching Capacity 1500 VA resistive load Mechanical Lifetime 107 switching cycles Creeping Distance and Clearance EN 50178 at pollution grade 2 over voltage category 3...

Страница 14: ...rical Lifetime 105 switching cycles DC 24V 2A 105 switching cycles DC 24V 2A Creeping Distance and Clearance EN 50178 at pollution grade 2 over voltage category 3 250V Basis isolation over voltage cat...