!PPENDIX
3*
6
# ' #
3700 TRIP CIR'T SUPERVISION
3701 TRIP SUP
Trip circuit supervision
OFF
[ ] off
ON
[ ] on
3702 T FAIL TC
Delay of trip circuit failure message
min. 1
s
max. 900
¬¬¬¬
¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
3800 FAULT LOCATION
3802 START
Start condition for fault locator
DROP-OFF or TRIP [ ] Drop-off or trip
TRIP COMMAND
[ ] Trip command
¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
3900 BREAKER FAILURE PROTEC.
3901 B/F PROT.
Circuit breaker failure protection
OFF
[ ] off
ON
[ ] on
3902 INT ORIGIN
B/F prot. with internal trip
ON
[ ] on
OFF
[ ] off
3903 EXT ORIGIN
B/F prot. with external trip (via BI)
ON
[ ] on
OFF
[ ] off
3904 CONTR ORIG
B/F prot. with control switch off
OFF
[ ] off
ON
[ ] on
3905 AUX CONT.
B/F prot. with CB auxiliary contacts
OFF
[ ] off
ON
[ ] on
3907 T-B/F
Delay time T-B/F
min. 0.06
s
max. 60.00/Ô
¬¬¬¬