/PERATING INSTRUCTIONS
3*
6
# ' #
0UTTING THE RELAY INTO OPERATION
!LL SETTING VALUES SHOULD BE CHECKED AGAIN IN CASE
THEY WERE ALTERED DURING THE TESTS 0ARTICULARLY CHECK
THAT ALL DESIRED PROTECTION FUNCTIONS HAVE BEEN PRO
GRAMMED IN THE CONFIGURATION PARAMETERS ADDRESS
BLOCKS AND REFER TO 3ECTION %NSURE THAT
THE TRIP TIMES ARE NOT SET TO
0
FOR THOSE FUNCTIONS OR
STAGES WHICH SHOULD TRIP AND THAT ALL DESIRED PROTEC
TION FUNCTIONS HAVE BEEN SWITCHED
/.
4HE COUNTERS FOR CIRCUIT BREAKER OPERATION STATISTICS
SHOULD BE ERASED ADDRESS BLOCK REFER TO 3ECTION
4HE COUNTER VALUES FOR ACTIVE AND REACTIVE EN
ERGY ARE IF NECESSARY READ OUT WRITTEN DOWN AND SET
TO ZERO
4HE INDICATIONS ON THE FRONT PLATE CAN BE RESET BY
THE 2%3%4 KEY SO THAT THEY FURTHERMORE INDICATE
ONLY REAL FAULTS 7HILE PUSHING THE 2%3%4 KEY THE
MARSHALLABLE ,%$S ON THE FRONT PLATE ARE ILLUMI
NATED PROVIDING A LAMP TEST !T THE SAME TIME SPON
TANEOUS FAULT MESSAGES IN THE DISPLAY IF ANY ARE
CANCELLED
0USH THE KEY
2
IF NECESSARY SEVERAL TIMES REPEATED
TO RETURN TO THE BASIC DIAGRAM 4HE DISPLAY SHOWS
THE FEEDER MIMIC DIAGRAM 4HE HEADLINE INDICATES
THE COMMAND SOURCE WHICH IS ACTIVATED FOR CONTROL
AND THE BOTTOM LINE SHOWS THE BAR DIAGRAM FOR INDI
CATION OF THE LARGEST PHASE CURRENT BASIC DIAGRAM
RESP AN OVERVIEW OF THE ACTUAL OPERATION MEASURED
VALUES BASIC DIAGRAM 3CROLLING BETWEEN THE TWO
PICTURES IS POSSIBLE WITH
#HECK THAT THE MODULE IS PROPERLY INSERTED 4HE
GREEN ,%$ MUST BE ON ON THE FRONT THE RED ,%$ MUST
NOT BE ON
#LOSE HOUSING COVER
!LL TERMINAL SCREWS
EVEN THOSE NOT IN USE
MUST
BE TIGHTENED
)F A TEST SWITCH IS AVAILABLE THEN THIS MUST BE IN THE
OPERATING POSITION
4HE RELAY IS NOW READY FOR OPERATION