!PPENDIX
3*
6
# ' #
1160 BRK CLOSED
Closed breaker current threshold
min. 0.04
I/In
max. 1.00
¬¬¬¬
1165 I-STRT-DET
Threshold of start-up detection
min. 0.60
I/In
max. 10.00
¬¬¬¬
¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
1200 O/C PROT. PHASES
1201 O/C PHASES
O/C protection for phase faults
ON
[ ] on
OFF
[ ] off
1202 I>>
Pick-up value of the high-set stage I>>
min. 0.10
I/In
max. 25.00
¬¬¬¬
1203 T-I>>
Trip time delay of the high-set stage I>>
min. 0.00
s
max. 60.00/Ô
¬¬¬¬
1206 MEAS.REPET
Measurement repetition
NO
[ ] no
YES
[ ] yes
1212 I>
Pick-up value of the overcurrent stage I>
min. 0.10
I/In
max. 25.00/Ô
¬¬¬¬
1213 T-I>
Trip time delay of the overcurrent stage I>
min. 0.00
s
max. 60.00/Ô
¬¬¬¬
1214 Ip
Pick-up value inverse time O/C stage Ip
min. 0.10
I/In
max. 4.00/Ô
¬¬¬¬
1215 T-Ip
Trip time delay inverse time O/C stage Ip
min. 0.05
s
max. 3.20/Ô
¬¬¬¬
1216 D Ip
Trip time delay inverse time O/C stage Ip/ANSI
min. 0.50
max. 15.00/Ô
¬¬¬¬
1217 RMS FORMAT
RMS format for inverse time O/C protection
FUNDAMENTAL
[ ] Fundamental
TRUE RMS
[ ] True rms
1218 CHARACTER.
Characteristic of the O/C stage Ip
NORMAL INVERSE
[ ] Normal inverse
VERY INVERSE
[ ] Very inverse
EXTREMELY INVERS [ ] Extremely inverse
www
. ElectricalPartManuals