)NSTALLATION INSTRUCTIONS
3*
6
# ' #
#ONFIGURATION OF THE PROTECTIVE FUNCTIONS
)NTRODUCTION
4HE
DEVICE
3* IS CAPABLE OF PROVIDING A SERIES
OF
PROTECTION
AND ADDITIONAL FUNCTIONS 4HE SCOPE OF
THE HARD AND FIRM WARE IS MATCHED TO THESE FUNC
TIONS !DDITIONALLY THE
CONTROL
FUNCTIONS CAN BE
MATCHED TO THE ON SITE CONDITIONS &URTHERMORE IN
DIVIDUAL FUNCTIONS CAN BE SET CONFIGURED TO BE EF
FECTIVE OR NON EFFECTIVE OR THE INTERACTION OF THE
FUNCTIONS CAN BE MODIFIED BY CONFIGURATION PARAME
TERS !DDITIONALLY THE RELAY CAN BE ADAPTED TO THE
SYSTEM FREQUENCY
ST EXAMPLE FOR CONFIGURATION OF THE SCOPE OF THE DE
VICE
!SSUME A NETWORK COMPRISING OVERHEAD LINES AND
CABLE SECTIONS 3INCE AUTO RECLOSURE IS ONLY APPLI
CABLE FOR THE OVERHEAD LINE SECTIONS THIS FUNCTION WILL
BE DE CONFIGURED FOR THE DEVICES PROTECTING THE
CABLE SECTIONS
ND EXAMPLE FOR THE INTERACTION OF THE FUNCTIONS
4HE HIGH CURRENT STAGE ) OF THE OVERCURRENT TIME
PROTECTION SHOULD OPERATE BEFORE AUTOMATIC RECLOS
URE THE REMAINING STAGES SHOULD NOT 4HE DEVICE WILL
BE INFORMED OF THIS CONDITION DURING CONFIGURATION
RD EXAMPLE FOR MATCHING OF THE CONTROL FUNCTIONS TO
THE SWITCHGEAR
"Y SELECTION OF THE FEEDER MIMIC DIAGRAM THE POSI
TION FEEDBACK SIGNALS ARE ASSIGNED TO THE REQUIRED
BINARY INPUT
4HE CONFIGURATION PARAMETERS ARE INPUT THROUGH THE
INTEGRATED OPERATION KEYBOARD AT THE FRONT OF THE DE
VICE OR BY MEANS OF A PERSONAL COMPUTER CONNECTED
TO THE FRONT INTERFACE 4HE USE OF THE INTEGRATED OP
ERATING KEYBOARD IS DESCRIBED IN DETAIL IN 3ECTION
!LTERATION OF THE PROGRAMMED PARAMETERS RE
QUIRES THE INPUT OF THE CODE WORD WITH LEVEL SEE
3ECTION 7ITHOUT CODE WORD THE SETTING CAN
BE READ OUT BUT NOT ALTERED
&OR THE PURPOSE OF CONFIGURATION ADDRESS BLOCKS
AND ARE PROVIDED /NE CAN ACCESS THE BEGINNING
OF THE CONFIGURATION BLOCKS FROM THE
-%.5
DOUBLE ARROW KEY
OPTION
#/.&)'52!4)/.
OPTION
3#/0% /& &5.#4)/.3 AS DE
SCRIBED IN 3ECTION REFER ALSO TO &IGURES AND
7ITHIN THE BLOCK ONE CAN MOVE THE CURSOR WITH
n
OR
m
AND THUS REACH THE INDIVIDUAL ADDRESSES FOR
CONFIGURATION PARAMETERS )N THE FOLLOWING SECTIONS
EACH ADDRESS IS SHOWN IN A BOX AND EXPLAINED )N THE
FIRST LINE OF EACH ADDRESS BEHIND THE ADDRESS NUM
BER STANDS THE ASSOCIATED DEVICE FUNCTION )N THE
SECOND LINE IS THE ASSOCIATED TEXT EG
%8)34
)F
THIS TEXT IS APPROPRIATE THE ARROW KEYS
m
OR
n
CAN BE
USED TO PAGE TO THE NEXT ADDRESS )F THE TEXT SHOULD
BE ALTERED PRESS THE .O KEY
.
AN ALTERNATIVE TEXT
THEN APPEARS EG
./. %8)34
4HERE MAY BE
FURTHER ALTERNATIVES WHICH CAN THEN BE DISPLAYED BY
REPEATED DEPRESSION OF THE .O KEY
.
4HE RE
QUIRED ALTERNATIVE
MUST BE CONFIRMED WITH THE KEY
%
7ITH THE BACKSPACE KEY
2
ONE GOES BACK TO THE
HIGHER MENU LEVEL #/.&)'52!4)/. THE MENU OP
TION
WILL LEAD TO ADDRESS BLOCK WITH FURTHER AD
DRESSES THE SETTING OF WHICH MAY BE ALTERED OR NOT
4HE CONFIGURATION PROCEDURE CAN BE ENDED AT ANY
TIME BY THE KEY COMBINATION
& %
IE DEPRESSING THE
FUNCTION KEY
&
FOLLOWED BY THE ENTRY KEY
%
4HE DIS
PLAY SHOWS THE QUESTION 3!6% .%7 3%44).'3
#ONFIRM WITH THE 9ES KEY
*9
THAT THE NEW SET
TINGS SHALL BECOME VALID NOW )F YOU PRESS THE
.O KEY
.
INSTEAD CODE WORD OPERATION WILL BE
ABORTED IE ALL ALTERATIONS WHICH HAVE BEEN
CHANGED SINCE THE LAST CODE WORD ENTRY ARE LOST
4HUS ERRONEOUS ALTERATIONS CAN BE MADE INEFFEC
TIVE
)F ONE TRIES TO LEAVE THE SETTING RANGE FOR THE CONFIGU
RATION BLOCKS IE ADDRESS BLOCKS TO BY TRYING
TO RETURN TO THE MAIN MENU THE DISPLAY SHOWS THE
QUESTION %.$ /& #/$%7/2$ /0%2!4)/.
0RESS THE .O KEY
.
TO CONTINUE CONFIGURATION )F
YOU PRESS THE 9ES KEY
*9
INSTEAD ANOTHER QUES
TION APPEARS 3!6% .%7 3%44).'3 .OW YOU
CAN CONFIRM WITH
*9
OR ABORT WITH
.
AS DESCRIBED
ABOVE
7HEN ONE EXITS THE SETTING PROGRAM THE ALTERED PA
RAMETERS WHICH UNTIL THEN HAVE BEEN STORED IN VOLA
TILE MEMORIES ARE THEN PERMANENTLY SECURED IN %%
02/-S AND PROTECTED AGAINST POWER OUTAGE 4HE
PROCESSOR SYSTEM WILL RESET AND RE START $URING
RE START THE DEVICE IS NOT OPERATIONAL