!PPENDIX
3*
6
# ' #
3403 M/C BLK
AR block with manual / control close
YES
[ ] yes
NO
[ ] no
3405 T-RECLAIM
Reclaim time after successful AR
min. 0.50
s
max. 320.00
¬¬¬¬
3406 T-LOCK
Lock-out time after unsuccessful AR
min. 0.50
s
max. 320.00/Ô
¬¬¬¬
3407 T-BLOC M/C
AR: blocking duration with manual close
min. 0.50
s
max. 320.00
¬¬¬¬
3412 CB? 1.TRIP
CB ready interrogation at 1st trip command
NO
[ ] no
YES
[ ] yes
3413 CB? CLOSE
CB ready interrogation before reclosing
CB? NEVER
[ ] CB? never
CB? WITH EACH AR [ ] CB? with each AR
CB? WITH 2nd AR [ ] CB? with 2nd AR
3415 T-CB-SUPV
Circuit breaker supervision time
min. 0.10
s
max. 320.00
¬¬¬¬
3424 RAR T-ACT.
Rapid auto-reclose action time
min. 0.01
s
max. 320.00/Ô
¬¬¬¬
3425 RAR T-PHA.
Dead time after trip by phase fault stage
min. 0.01
s
max. 320.00
¬¬¬¬
3426 RAR T-EAR.
Dead time after trip by earth fault stage
min. 0.01
s
max. 320.00
¬¬¬¬
3443 DAR SHOT E
Permissible DAR shots after earth faults
min. 0
max. 9
¬¬¬¬
3444 DAR SHOT P
Permissible DAR shots after phase faults
min. 0
max. 9
¬¬¬¬
3445 DAR T-ACT.
Delayed auto-reclose action time
min. 0.01
s
max. 320.00/Ô
¬¬¬¬
3446 DAR T-EAR.
Dead time after trip by earth fault stage
min. 0.01
s
max. 1800.00
¬¬¬¬
3447 DAR T-PHA.
Dead time after trip by phase fault stage
min. 0.01
s
max. 1800.00
¬¬¬¬