Addr.
Parameter
Setting Options
Default Setting
Comments
3702
59-1-Vph PICKUP
1.0 .. 170.0 V
85.0 V
59-1 Pickup Overvoltage (phase-
ground)
3703
59-1-Vph DELAY
0.00 .. 100.00 sec
2.00 sec
59-1 Time Delay
3704
59-2-Vph PICKUP
1.0 .. 170.0 V
100.0 V
59-2 Pickup Overvoltage (phase-
ground)
3705
59-2-Vph DELAY
0.00 .. 100.00 sec
1.00 sec
59-2 Time Delay
3709A
59-Vph RESET
0.30 .. 0.99
0.98
Reset ratio
3711
59-Vph-ph Mode
OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF
Operating mode Vph-ph over-
voltage prot.
3712
59-1-Vpp PICKUP
2.0 .. 220.0 V
150.0 V
59-1 Pickup Overvoltage (phase-
phase)
3713
59-1-Vpp DELAY
0.00 .. 100.00 sec
2.00 sec
59-1 Time Delay
3714
59-2-Vpp PICKUP
2.0 .. 220.0 V
175.0 V
59-2 Pickup Overvoltage (phase-
phase)
3715
59-2-Vpp DELAY
0.00 .. 100.00 sec
1.00 sec
59-2 Time Delay
3719A
59-Vpp RESET
0.30 .. 0.99
0.98
Reset ratio
3721
59G-3V0 (or Vx)
OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF
Operating mode 3V0 overvoltage
3722
59G-1-3V0PICKUP
1.0 .. 220.0 V
30.0 V
59G-1 Pickup 3V0 (zero seq.)
3723
59G-1-3V0 DELAY
0.00 .. 100.00 sec
2.00 sec
59G-1 Time Delay
3724
59G-2-3V0PICKUP
1.0 .. 220.0 V
50.0 V
59G-2 Pickup 3V0 (zero seq.)
3725
59G-2-3V0 DELAY
0.00 .. 100.00 sec
1.00 sec
59G-2 Time Delay
3728A
59G-3Vo Stabil.
ON
OFF
ON
59G: Stabilization 3Vo-Measure-
ment
3729A
59G RESET
0.30 .. 0.99
0.95
Reset ratio
3731
59-V1 Mode
OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF
Operating mode V1 overvoltage
prot.
3732
59-1-V1 PICKUP
2.0 .. 220.0 V
150.0 V
59-1 Pickup Overvoltage (pos.
seq.)
3733
59-1-V1 DELAY
0.00 .. 100.00 sec
2.00 sec
59-1 Time Delay
3734
59-2-V1 PICKUP
2.0 .. 220.0 V
175.0 V
59-2 Pickup Overvoltage (pos.
seq.)
3735
59-2-V1 DELAY
0.00 .. 100.00 sec
1.00 sec
59-2 Time Delay
3739A
59-V1 RESET
0.30 .. 0.99
0.98
Reset ratio
3741
59-V2 Mode
OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF
Operating mode V2 overvoltage
prot.
3742
59-1-V2 PICKUP
2.0 .. 220.0 V
30.0 V
59-1 Pickup Overvoltage (neg.
seq.)
3743
59-1-V2 DELAY
0.00 .. 100.00 sec
2.00 sec
59-1 Time Delay
3744
59-2-V2 PICKUP
2.0 .. 220.0 V
50.0 V
59-2 Pickup Overvoltage (neg.
seq.)
Functions
2.8 Undervoltage and Overvoltage Protection (optional) 27/59
118
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Содержание SIPROTEC 4 7SD80
Страница 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...