Functional Description
Changing Setting Groups
During operation the user can switch back and forth setting groups locally, via the operator panel, binary
inputs (if so configured), the service interface using a personal computer, or via the system interface. For
reasons of safety it is not possible to change between setting groups during a power system fault.
A setting group includes the setting values for all functions that have been selected as
Enabled
during
). In 7SD80 relays, four independent setting groups (A to D)
are available. While setting values may vary, the selected functions of each setting group remain the same.
Setting Notes
General
If setting group change option is not required, Group A is the default selection. Then, the rest of this section is
not applicable.
If the changeover option is desired, group changeover must be set to
Grp Chge OPTION
=
Enabled
(address 103) when the function extent is configured. For the setting of the function parameters, each of the
required setting groups A to D (a maximum of 4) must be configured in sequence. The SIPROTEC 4 System
Description gives further information on how to copy setting groups or reset them to their status at delivery
and also how to change from one setting group to another.
Section
of this manual tells you how to change between several setting groups
externally via binary inputs.
Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
301
ACTIVE GROUP
Group A
Group B
Group C
Group D
Group A
Active Setting Group is
302
CHANGE
Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A
Change to Another Setting Group
Information List
No.
Information
Type of
Informa-
tion
Comments
-
P-GrpA act
IntSP
Setting Group A is active
-
P-GrpB act
IntSP
Setting Group B is active
-
P-GrpC act
IntSP
Setting Group C is active
-
P-GrpD act
IntSP
Setting Group D is active
7
>Set Group Bit0
SP
>Setting Group Select Bit 0
8
>Set Group Bit1
SP
>Setting Group Select Bit 1
2.1.5.1
2.1.5.2
2.1.5.3
2.1.5.4
Functions
2.1 General
SIPROTEC 4, 7SD80, Manual
41
E50417-G1100-C474-A2, Edition 02.2018
Содержание SIPROTEC 4 7SD80
Страница 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...