IEC 60870-5-103 redundant, RS485
Isolated interface for data transfer to a control center
Terminal
Back case bottom, mounting location "B", RJ45 socket
Test voltage (PELV)
500 V; 50 Hz
Transmission speed
min. 2,400 Bd, max. 57,600 Bd;
factory setting 19,200 Bd
Bridgeable distance
max. 1 km
Profibus RS485 (DP)
Terminal
Back case bottom, mounting location "B”, 9- pin DSUB socket
Test voltage (PELV)
500 V; 50 Hz
Transmission speed
Up to 1.5 MBd
Bridgeable distance
1 000 m (3 300 ft) at ≤ 93.75 kBd
500 m (1 600 ft) at ≤ 187.5 kBd
200 m (660 ft) at ≤ 1.5 MBd
Profibus FO (DP)
FO connector type
ST connector
Double ring
Terminal
Back case bottom, mounting location "B”
Transmission speed
bis 1.5 MBd
Recommended:
> 500 kBd with normal casing
Optical wavelength
λ = 820 nm
Laser Class 1 according to EN 60825-1/-2
When using glass fiber 50/125 μm or glass fiber 62.5/125 μm
Permissible optical signal attenuation
max. 8 dB, with glass fiber 62.5/125 μm
Bridgeable distance
max. 1.5 km
DNP3.0 /MODBUS RS485
Terminal
Back case bottom, mounting location "B”, 9- pin DSUB socket
Test voltage (PELV)
500 V; 50 Hz
Transmission speed
up to 19,200 Bd
Bridgeable distance
max. 1 km
DNP3.0 /MODBUS FO
FO connector type
ST connector transmitter/receiver
Terminal
Back case bottom, mounting location "B”
Transmission speed
up to 19,200 Bd
Optical wavelength
λ = 820 nm
Laser Class 1 according to EN 60825-1/-2
When using glass fiber 50 μm/125 μm or glass fiber 62.5/125 μm
Permissible optical signal attenuation
max. 8 dB, with glass fiber 62.5/125 μm
Bridgeable distance
max. 1.5 km
Ethernet electrical (EN 100) for DIGSI, IEC61850
Terminal
Back case bottom, mounting location "B”,
2 x RJ45 socket
100BaseT according to IEEE802.3
Technical Data
4.1 General Device Data
SIPROTEC 4, 7SD80, Manual
253
E50417-G1100-C474-A2, Edition 02.2018
Содержание SIPROTEC 4 7SD80
Страница 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...