No.
Information
Type of
Informa-
tion
Comments
32125
87(N)L Gen.TRIP
OUT
87(N)L General TRIP
32126
87N L block
OUT
87N L: Protection is blocked
32127
87N L OFF
OUT
87N L: Protection is switched off
32128
87N L 3V0>
OUT
87N L: detection 3V0> pickup
32129
87N L Forward
OUT
87N L: detection Forward
32130
87N L Reverse
OUT
87N L: detection Reverse
32131
87N L UndefDir
OUT
87N L: detection Undef. Direction
32132
87N L rec. blk
OUT
87N L: receive blocking
32133
87N L send blk
OUT
87N L: send blocking
32134
87N L PU
OUT
87N L: pickup
32150
87L ISTAT> C
OUT
87L ISTAT> C
Differential Protection Test and Commissioning
Differential Protection Test
General
If differential protection test mode (test mode in the following) is activated, the differential protection is
blocked in the entire system. Depending on the configuration, the overcurrent protection acts as emergency
function.
In the local device all currents from the other devices are set to zero. The local device only evaluates the locally
measured currents, interprets them as differential current but does not send them to the other devices. This
enables measuring the thresholds of the differential protection. Moreover, the test mode prevents in the local
device that tripping of the differential protection generates a transfer trip signal.
The test mode can be activated/deactivated as follows:
•
Operation panel: Menu Control/Taggings/Set: “Test mode”
•
Via binary inputs (no. 3197
>Test 87 ON
, no. 3198
>Test 87 OFF
) if this was routed
•
In DIGSI with Control / Taggings: “Diff: Test mode”
The test mode status of the other device of the line protection system is indicated on the local device by the
indication
Test 87 remote
(No. 3192).
Functional Description
Below, the logic is shown in a simplified way:
[logik-testmodus, 1, en_US]
Figure 2-17
Logic diagram of the test mode
Depending on the way used for controlling the test mode, either the indication
Test 87 ON/off
(no. 3199)
or
Test 87 ONoffBI
(no. 3200) is generated. The way used for deactivating the test mode always has to be
2.2.7
2.2.7.1
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
SIPROTEC 4, 7SD80, Manual
65
E50417-G1100-C474-A2, Edition 02.2018
Содержание SIPROTEC 4 7SD80
Страница 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...