Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
3758 CURR.SUP 27-Vph
27/59 O/U Volt.
ON
OFF
ON
Current supervision (Vph-
g)
3759A 27-Vph RESET
27/59 O/U Volt.
1.01 .. 1.20
1.05
Reset ratio
3761 27-Vph-ph Mode
27/59 O/U Volt.
OFF
Alarm Only
ON
V<Alarm V<<Trip
OFF
Operating mode Vph-ph
undervoltage prot.
3762 27-1-Vpp PICKUP
27/59 O/U Volt.
1.0 .. 175.0 V; 0
50.0 V
27-1 Pickup Undervoltage
(phase-phase)
3763 27-1-Vpp DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
2.00 sec
27-1 Time Delay
3764 27-2-Vpp PICKUP
27/59 O/U Volt.
1.0 .. 175.0 V; 0
17.0 V
27-2 Pickup Undervoltage
(phase-phase)
3765 27-2-Vpp DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
1.00 sec
27-2 Time Delay
3768 CURR.SUP 27-Vpp
27/59 O/U Volt.
ON
OFF
ON
Current supervision (Vph-
ph)
3769A 27-Vph-ph RESET
27/59 O/U Volt.
1.01 .. 1.20
1.05
Reset ratio
3771 27-V1 Mode
27/59 O/U Volt.
OFF
Alarm Only
ON
V<Alarm V<<Trip
OFF
Operating mode V1
Undervoltage prot.
3772 27-1-V1 PICKUP
27/59 O/U Volt.
1.0 .. 100.0 V; 0
30.0 V
27-1 Pickup Undervoltage
(pos. seq.)
3773 27-1-V1 DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
2.00 sec
27-1 Time Delay
3774 27-2-V1 PICKUP
27/59 O/U Volt.
1.0 .. 100.0 V; 0
10.0 V
27-2 Pickup Undervoltage
(pos. seq.)
3775 27-2-V1 DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
1.00 sec
27-2 Time Delay
3778 CURR.SUP. 27-V1
27/59 O/U Volt.
ON
OFF
ON
Current supervision (V1)
3779A 27-V1 RESET
27/59 O/U Volt.
1.01 .. 1.20
1.05
Reset ratio
3901 FCT 50BF Break.
50BF BkrFailure
ON
OFF
ON
50BF Breaker Failure
Protection
3902 50BF PICKUP
50BF BkrFailure 1A
0.05 .. 20.00 A
0.10 A
50BF Pickup current
threshold
5A
0.25 .. 100.00 A
0.50 A
3905 50BF-1 Delay 3p
50BF BkrFailure
0.00 .. 30.00 sec; ∞ 0.00 sec
Delay after 3pole start for
local trip
3906 50BF-2 Delay
50BF BkrFailure
0.00 .. 30.00 sec; ∞ 0.15 sec
Delay of 2nd element for
busbar trip
3907 T3-BkrDefective
50BF BkrFailure
0.00 .. 30.00 sec; ∞ 0.00 sec
Delay for start with defec-
tive bkr.
3908 Trip BkrDefect.
50BF BkrFailure
NO
with Local trip
with Bus trip
w/Local&Bustrip
NO
Trip output selection with
defective bkr
3909 Chk BRK CONTACT 50BF BkrFailure
NO
YES
YES
Check Breaker contacts
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SD80, Manual
349
E50417-G1100-C474-A2, Edition 02.2018
Содержание SIPROTEC 4 7SD80
Страница 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...