Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
3722 59G-1-3V0PICKUP
27/59 O/U Volt.
1.0 .. 220.0 V; ∞
30.0 V
59G-1 Pickup 3V0 (zero
seq.)
3723 59G-1-3V0 DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
2.00 sec
59G-1 Time Delay
3724 59G-2-3V0PICKUP
27/59 O/U Volt.
1.0 .. 220.0 V; ∞
50.0 V
59G-2 Pickup 3V0 (zero
seq.)
3725 59G-2-3V0 DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
1.00 sec
59G-2 Time Delay
3728A 59G-3Vo Stabil.
27/59 O/U Volt.
ON
OFF
ON
59G: Stabilization 3Vo-
Measurement
3729A 59G RESET
27/59 O/U Volt.
0.30 .. 0.99
0.95
Reset ratio
3731 59-V1 Mode
27/59 O/U Volt.
OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF
Operating mode V1 over-
voltage prot.
3732 59-1-V1 PICKUP
27/59 O/U Volt.
2.0 .. 220.0 V; ∞
150.0 V
59-1 Pickup Overvoltage
(pos. seq.)
3733 59-1-V1 DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
2.00 sec
59-1 Time Delay
3734 59-2-V1 PICKUP
27/59 O/U Volt.
2.0 .. 220.0 V; ∞
175.0 V
59-2 Pickup Overvoltage
(pos. seq.)
3735 59-2-V1 DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
1.00 sec
59-2 Time Delay
3739A 59-V1 RESET
27/59 O/U Volt.
0.30 .. 0.99
0.98
Reset ratio
3741 59-V2 Mode
27/59 O/U Volt.
OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF
Operating mode V2 over-
voltage prot.
3742 59-1-V2 PICKUP
27/59 O/U Volt.
2.0 .. 220.0 V; ∞
30.0 V
59-1 Pickup Overvoltage
(neg. seq.)
3743 59-1-V2 DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
2.00 sec
59-1 Time Delay
3744 59-2-V2 PICKUP
27/59 O/U Volt.
2.0 .. 220.0 V; ∞
50.0 V
59-2 Pickup Overvoltage
(neg. seq.)
3745 59-2-V2 DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
1.00 sec
59-2 Time Delay
3749A 59-V2 RESET
27/59 O/U Volt.
0.30 .. 0.99
0.98
Reset ratio
3751 27-Vph-g Mode
27/59 O/U Volt.
OFF
Alarm Only
ON
V<Alarm V<<Trip
OFF
Operating mode Vph-g
undervoltage prot.
3752 27-1-Vph PICKUP
27/59 O/U Volt.
1.0 .. 100.0 V; 0
30.0 V
27-1 Pickup Undervoltage
(phase-neutral)
3753 27-1-Vph DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
2.00 sec
27-1 Time Delay
3754 27-2-Vph PICKUP
27/59 O/U Volt.
1.0 .. 100.0 V; 0
10.0 V
27-2 Pickup Undervoltage
(phase-neutral)
3755 27-2-Vph DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
1.00 sec
27-2 Time Delay
Functions, Settings, Information
F.2 Settings
348
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Содержание SIPROTEC 4 7SD80
Страница 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...