Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
3611 81 O/U FREQ. f2
81 O/U Freq.
ON: Alarm only
ON: with Trip
OFF
ON: Alarm only
81 Over/Under Frequency
Prot. element f2
3612 81-2 PICKUP
81 O/U Freq.
45.50 .. 54.50 Hz
49.00 Hz
81-2 Pickup
3613 81-2 PICKUP
81 O/U Freq.
55.50 .. 64.50 Hz
57.00 Hz
81-2 Pickup
3614 81-2 DELAY
81 O/U Freq.
0.00 .. 600.00 sec
30.00 sec
81-2 Time Delay
3621 81 O/U FREQ. f3
81 O/U Freq.
ON: Alarm only
ON: with Trip
OFF
ON: Alarm only
81 Over/Under Frequency
Prot. element f3
3622 81-3 PICKUP
81 O/U Freq.
45.50 .. 54.50 Hz
47.50 Hz
81-3 Pickup
3623 81-3 PICKUP
81 O/U Freq.
55.50 .. 64.50 Hz
59.50 Hz
81-3 Pickup
3624 81-3 DELAY
81 O/U Freq.
0.00 .. 600.00 sec
3.00 sec
81-3 Time delay
3631 81 O/U FREQ. f4
81 O/U Freq.
ON: Alarm only
ON: with Trip
OFF
ON: Alarm only
81 Over/Under Frequency
Prot. element f4
3632 81-4 PICKUP
81 O/U Freq.
45.50 .. 54.50 Hz
51.00 Hz
81-4 Pickup
3633 81-4 PICKUP
81 O/U Freq.
55.50 .. 64.50 Hz
62.00 Hz
81-4 Pickup
3634 81-4 DELAY
81 O/U Freq.
0.00 .. 600.00 sec
30.00 sec
81-4 Time delay
3701 59-Vph-g Mode
27/59 O/U Volt.
OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF
Operating mode Vph-g
overvoltage prot.
3702 59-1-Vph PICKUP
27/59 O/U Volt.
1.0 .. 170.0 V; ∞
85.0 V
59-1 Pickup Overvoltage
(phase-ground)
3703 59-1-Vph DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
2.00 sec
59-1 Time Delay
3704 59-2-Vph PICKUP
27/59 O/U Volt.
1.0 .. 170.0 V; ∞
100.0 V
59-2 Pickup Overvoltage
(phase-ground)
3705 59-2-Vph DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
1.00 sec
59-2 Time Delay
3709A 59-Vph RESET
27/59 O/U Volt.
0.30 .. 0.99
0.98
Reset ratio
3711 59-Vph-ph Mode
27/59 O/U Volt.
OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF
Operating mode Vph-ph
overvoltage prot.
3712 59-1-Vpp PICKUP
27/59 O/U Volt.
2.0 .. 220.0 V; ∞
150.0 V
59-1 Pickup Overvoltage
(phase-phase)
3713 59-1-Vpp DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
2.00 sec
59-1 Time Delay
3714 59-2-Vpp PICKUP
27/59 O/U Volt.
2.0 .. 220.0 V; ∞
175.0 V
59-2 Pickup Overvoltage
(phase-phase)
3715 59-2-Vpp DELAY
27/59 O/U Volt.
0.00 .. 100.00 sec;
∞
1.00 sec
59-2 Time Delay
3719A 59-Vpp RESET
27/59 O/U Volt.
0.30 .. 0.99
0.98
Reset ratio
3721 59G-3V0 (or Vx)
27/59 O/U Volt.
OFF
Alarm Only
ON
V>Alarm V>>Trip
OFF
Operating mode 3V0
overvoltage
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SD80, Manual
347
E50417-G1100-C474-A2, Edition 02.2018
Содержание SIPROTEC 4 7SD80
Страница 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...