![Siemens SIPROTEC 4 7SD80 Скачать руководство пользователя страница 87](http://html.mh-extra.com/html/siemens/siprotec-4-7sd80/siprotec-4-7sd80_manual_382509087.webp)
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2628
67(N)-B2 Pil/BI
NO
YES
NO
Instantaneous trip via Pilot
Prot./BI
2630
Op.Mode 51(N)-B
ON
Only Emer. prot
OFF
OFF
Operating Mode 51(N)-B
2630
Op.Mode67(N)TOC
ON
Only Emer. prot
OFF
OFF
Operating Mode 67(N)-
TOC
2631
67(N)-TOC Dir.
Non-Directional
Forward
Reverse
Non-Directional
67(N)-TOC Direction
2632
67(N)-TOCon FFM
Non-Directional
BLOCKED
BLOCKED
67(N)-TOC Direct. stage on
Fuse Failure
2633
51-B PICKUP
1A
0.10 .. 4.00 A; ∞
∞ A
51-B Pickup
5A
0.50 .. 20.00 A; ∞
∞ A
2633
67-TOC PICKUP
1A
0.10 .. 4.00 A; ∞
∞ A
67-TOC Pickup threshold
5A
0.50 .. 20.00 A; ∞
∞ A
2634
51-B TD IEC
0.05 .. 3.00 sec; ∞
0.50 sec
51-B Time Dial for IEC char-
acteristic
2634
67-TOC TD IEC
0.05 .. 3.00 sec; ∞
0.50 sec
67-TOC Time Dial for IEC
characteristic
2635
51-B TD ANSI
0.50 .. 15.00 ; ∞
5.00
51-B Time Dial for ANSI
characteristic
2635
67-TOC TD ANSI
0.50 .. 15.00 ; ∞
5.00
67-TOC Time Dial for ANSI
characteristic
2636
51-B AddT-DELAY
0.00 .. 30.00 sec
5.00 sec
51-B Additional Time Delay
2636
67-TOC AddTDel.
0.00 .. 30.00 sec
5.00 sec
67-TOC Additional Time
Delay
2637
51-B Inrush
NO
YES
NO
51-B Inrush blocking
2637
67-TOC Inrush
NO
YES
NO
67-TOC Inrush blocking
2638
51N-B PICKUP
1A
0.05 .. 4.00 A; ∞
∞ A
51N-B Pickup
5A
0.25 .. 20.00 A; ∞
∞ A
2638
67N-TOC PICKUP
1A
0.05 .. 4.00 A; ∞
∞ A
67N-TOC Pickup threshold
5A
0.25 .. 20.00 A; ∞
∞ A
2639
51N-B TD IEC
0.05 .. 3.00 sec; ∞
0.50 sec
51N-B Time Dial for IEC
characteristic
2639
67N-TOC TD IEC
0.05 .. 3.00 sec; ∞
0.50 sec
67N-TOC Time Dial for IEC
characteristic
2640
51N-B TD ANSI
0.50 .. 15.00 ; ∞
5.00
51N-B Time Dial for ANSI
characteristic
2640
67N-TOC TD ANSI
0.50 .. 15.00 ; ∞
5.00
67N-TOC Time Dial for
ANSI char.
2641
51N-B AddTdelay
0.00 .. 30.00 sec
0.00 sec
51N-B Additional Time
Delay
2641
67N-TOC AddTDel
0.00 .. 30.00 sec
0.00 sec
67N-TOC Additional Time
Delay
Functions
2.4 Backup overcurrent
SIPROTEC 4, 7SD80, Manual
87
E50417-G1100-C474-A2, Edition 02.2018
Содержание SIPROTEC 4 7SD80
Страница 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...