Parameter list
8.2 Parameter list
SINAMICS V20 Converter
248
Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling Data
set
Data
type
Acc.
Level
P1010[0...2]
Fixed frequency 10 [Hz] -550.00 - 550.00 0.00
U, T
-
DDS
Float 2
Defines fixed frequency setpoint 10.
Note:
See P1001
P1011[0...2]
Fixed frequency 11 [Hz] -550.00 - 550.00 0.00
U, T
-
DDS
Float 2
Defines fixed frequency setpoint 11.
Note:
See P1001
P1012[0...2]
Fixed frequency 12 [Hz] -550.00 - 550.00 0.00
U, T
-
DDS
Float 2
Defines fixed frequency setpoint 12.
Note:
See P1001
P1013[0...2]
Fixed frequency 13 [Hz] -550.00 - 550.00 0.00
U, T
-
DDS
Float 2
Defines fixed frequency setpoint 13.
Note:
See P1001
P1014[0...2]
Fixed frequency 14 [Hz] -550.00 - 550.00 0.00
U, T
-
DDS
Float 2
Defines fixed frequency setpoint 14.
Note:
See P1001
P1015[0...2]
Fixed frequency 15 [Hz] -550.00 - 550.00 0.00
U, T
-
DDS
Float 2
Defines fixed frequency setpoint 15.
Note:
See P1001
P1016[0...2]
Fixed frequency mode
1 - 2
1
T
-
DDS
U16
2
Fixed frequencies can be selected in two different modes. P1016 defines the mode.
1
Direct selection
2
Binary selection
Note:
See P1001 for description of how to use fixed frequencies.
P1020[0...2]
BI: Fixed frequency
selection Bit 0
0 - 4294967295 722.3
T
-
CDS
U32
3
Defines origin of fixed frequency selection.
Example:
= 722.0
Digital input 1 (requires P0701 to be set to 99, BICO)
= 722.1
Digital input 2 (requires P0702 to be set to 99, BICO)
= 722.2
Digital input 3 (requires P0703 to be set to 99, BICO)
= 722.3
Digital input 4 (requires P0704 to be set to 99, BICO)
Dependency: Accessible only if P0701 - P070x = 99 (function of digital inputs = BICO)
P1021[0...2]
BI: Fixed frequency
selection Bit 1
0 - 4294967295 722.4
T
-
CDS
U32
3
See P1020
P1022[0...2]
BI: Fixed frequency
selection Bit 2
0 - 4294967295 722.5
T
-
CDS
U32
3
See P1020
P1023[0...2]
BI: Fixed frequency
selection Bit 3
0 - 4294967295 722.6
T
-
CDS
U32
3
See P1020
Содержание SINAMICS V20 Inverter
Страница 1: ...SINAMICS V20 Converter ...
Страница 2: ......
Страница 8: ...Preface SINAMICS V20 Converter 6 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 346: ...Faults and alarms 9 2 Alarms SINAMICS V20 Converter 344 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 358: ...Technical specifications SINAMICS V20 Converter 356 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 426: ......