Parameter list
8.2 Parameter list
SINAMICS V20 Converter
298
Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling Data
set
Data
type
Acc.
Level
Note:
See P2201
P2216[0...2] Fixed PID setpoint mode 1 - 2
1
T
-
DDS
U16
2
Fixed frequencies for PID setpoint can be selected in two different modes. P2216 defines the mode.
1
Direct selection
2
Binary selection
P2220[0...2] BI: Fixed PID setpoint
select bit 0
0 - 4294967295
722.3
T
-
CDS
U32
3
Defines command source of fixed PID setpoint selection bit 0.
P2221[0...2] BI: Fixed PID setpoint
select bit 1
0 - 4294967295
722.4
T
-
CDS
U32
3
Defines command source of fixed PID setpoint selection bit 1.
P2222[0...2] BI: Fixed PID setpoint
select bit 2
0 - 4294967295
722.5
T
-
CDS
U32
3
Defines command source of fixed PID setpoint selection bit 2.
P2223[0...2] BI: Fixed PID setpoint
select bit 3
0 - 4294967295
722.6
T
-
CDS
U32
3
Defines command source of fixed PID setpoint selection bit 3.
r2224
CO: Actual fixed PID
setpoint [%]
-
-
-
-
-
Float 2
Displays total output of PID fixed setpoint selection.
Note:
r2224 = 100 % corresponds to 4000 hex.
r2225.0
BO: PID fixed frequency
status
-
-
-
-
-
U16
3
Displays the status of PID fixed frequencies.
Bit
Signal name
1 signal
0 signal
00
Status of FF
Yes
No
P2231[0...2] PID-MOP mode
0 - 3
0
U, T
-
DDS
U16
2
PID-MOP mode specification
Bit
Signal name
1 signal
0 signal
00
Setpoint store active
Yes
No
01
No On-state for MOP necessary
Yes
No
Note:
Defines the operation mode of the motorized potentiometer. See P2240.
P2232
Inhibit reverse direction of
PID-MOP
0 - 1
1
T
-
-
U16
2
Inhibits reverse setpoint selection of the PID-MOP.
0
Reverse direction is allowed
1
Reverse direction inhibited
Note:
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease
frequency).
P2235[0...2] BI: Enable PID-MOP (UP-
cmd)
0 - 4294967295
0
T
-
CDS
U32
3
Defines source of UP command.
Содержание SINAMICS V20 Inverter
Страница 1: ...SINAMICS V20 Converter ...
Страница 2: ......
Страница 8: ...Preface SINAMICS V20 Converter 6 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 346: ...Faults and alarms 9 2 Alarms SINAMICS V20 Converter 344 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 358: ...Technical specifications SINAMICS V20 Converter 356 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 426: ......