Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
78
Operating Instructions, 10/2019, A5E34559884-012
Setting application macros
Application macro AP010 - Simple pump applications
Parameter Description
Factory
default
Default for
AP010
Remarks
P1080[0] Minimum frequency
0
15
Converter running at a lower speed inhibited
P1300[0] Control mode
0
7
Quadratic V/f
P1110[0] BI: Inhibit negative frequen-
cy setpoint
0
1
Reverse pump rotation inhibited
P1210[0] Automatic restart
1
2
Restart after mains blackout
P1120[0] Ramp-up time
10
10
Ramp-up time from zero to maximum frequency
P1121[0] Ramp-down time
10
10
Ramp-down time from maximum frequency to zero
Application macro AP020 - Simple fan applications
Parameter Description
Factory
default
Default for
AP020
Remarks
P1110[0] BI: Inhibit negative frequency
setpoint
0
1
Reverse fan rotation inhibited
P1300[0] Control mode
0
7
Quadratic V/f
P1200[0] Flying start
0
2
Search for the speed of the running motor with a
heavy inertia load so that the motor runs up to the
setpoint
P1210[0] Automatic restart
1
2
Restart after mains blackout
P1080[0] Minimum frequency
0
20
Converter running at a lower speed inhibited
P1120[0] Ramp-up time
10
10
Ramp-up time from zero to maximum frequency
P1121[0] Ramp-down time
10
20
Ramp-down time from maximum frequency to zero
Содержание SINAMICS V20 Inverter
Страница 1: ...SINAMICS V20 Converter ...
Страница 2: ......
Страница 8: ...Preface SINAMICS V20 Converter 6 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 346: ...Faults and alarms 9 2 Alarms SINAMICS V20 Converter 344 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 358: ...Technical specifications SINAMICS V20 Converter 356 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 426: ......