Parameter list
8.2 Parameter list
SINAMICS V20 Converter
308
Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P2376[0...2] Motor staging delay over-
ride [%]
0.0 - 200.0
25.0
U, T
PERCEN
T
DDS
Float 3
P2376 as a percentage of PID setpoint. When the PID error r2273 exceeds this value, a motor is
staged/destaged irrespective of the delay timers.
Note:
The value of this parameter must always be larger than staging hysteresis P2373.
P2377[0...2] Motor staging lockout
timer [s]
0 - 650
30
U, T
-
DDS
U16 3
Time for which delay override is prevented after a motor has been staged or destaged.
This prevents a second staging event immediately after a first, being caused by the transient conditions
after the first staging event.
P2378[0...2] CO: Motor staging fre-
quency f_st [%]
0.0 - 120.0
50.0
U, T
PERCEN
T
DDS
Float 3
The frequency as a percentage of maximum frequency. During a (de) staging event, as the converter
ramps from maximum to minimum frequency (or vice versa) this is the frequency at which the digital out-
put is switched.
This is illustrated by the following diagrams.
Содержание SINAMICS V20 Inverter
Страница 1: ...SINAMICS V20 Converter ...
Страница 2: ......
Страница 8: ...Preface SINAMICS V20 Converter 6 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 346: ...Faults and alarms 9 2 Alarms SINAMICS V20 Converter 344 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 358: ...Technical specifications SINAMICS V20 Converter 356 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 426: ......