Communicating with the PLC
7.2 MODBUS communication
SINAMICS V20 Converter
186
Operating Instructions, 10/2019, A5E34559884-012
Basic converter settings
Parameter Function
Setting
P0010
Commissioning parameter
= 30: restores to factory settings
P0970
Factory reset
Possible settings:
= 1: resets all parameters (not user defaults) to their default
values
= 21: resets all parameters and all user defaults to factory
reset state
Note: Parameters P2010, P2021, P2023 retain their values after a
factory reset.
P0003
User access level
= 3
P0700
Selection of command source
= 5: USS/MODBUS on RS485
Factory default: 1 (operator panel)
P2010[0]
USS/MODBUS baudrate
Possible settings:
= 6: 9600 bps (factory default)
= 7: 19200 bps
= 8: 38400 bps
...
=12: 115200 bps
P2014[0]
USS/MODBUS telegram off time [ms] If time set to 0, no fault is generated (i.e. watchdog disabled).
P2021
Modbus address
Sets the unique address for the converter.
Range: 1 to 247 (factory default: 1)
P2022
Modbus reply timeout [ms]
Range: 0 to 10000 (factory default: 1000)
P2023
RS485 protocol selection
= 2: Modbus
Factory default: 1 (USS)
Note: After changing P2023, powercycle the converter. During the
powercycle, wait until LED has gone off or the display has gone
blank (may take a few seconds) before re-applying power. If P2023
has been changed via a PLC, make sure the change has been
saved to EEPROM via P0971.
r2024[0]
...
r2031[0]
USS/MODBUS error statistics
The state of the telegram information on RS485 is reported regard-
less of the protocol set in P2023.
r2018[0...7] CO: PZD from USS/ MODBUS on
RS485
Displays process data received via USS/MODBUS on RS485.
P2019[0...7] CI: PZD to USS/MODBUS on RS485
Displays process data transmitted via USS/MODBUS on RS485.
P2034
MODBUS parity on RS485
Sets the parity of MODBUS telegrams on RS485.
Possible settings:
= 0: no parity
= 1: odd parity
= 2: even parity
P2035
MODBUS stop bits on RS485
Sets the number of stop bits in MODBUS telegrams on RS485.
Possible settings:
= 1: 1 stop bit
= 2: 2 stop bits
Содержание SINAMICS V20 Inverter
Страница 1: ...SINAMICS V20 Converter ...
Страница 2: ......
Страница 8: ...Preface SINAMICS V20 Converter 6 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 346: ...Faults and alarms 9 2 Alarms SINAMICS V20 Converter 344 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 358: ...Technical specifications SINAMICS V20 Converter 356 Operating Instructions 10 2019 A5E34559884 012 ...
Страница 426: ......