Note
Shielding is not required if at least one of the following conditions is satisfied:
• The cables must not be longer than 1 m.
• The cables are routed flush with the rear metal panel of the control cabinet.
• In the control cabinet, the cables are routed separately from the signal cables.
6.2.2.2
Shield support with optional shield connection plate
Only use shielded connecting cables with the optional shield connection plate. It is
recommended that the cable is additionally fastened to the strain relief plate.
①
Screws for fastening the strain relief plate
②
Strain relief plate
③
Screws for fastening the optional shield connection plate
④
Optional shield connection plate with fastening for the shield connection clamp
Figure 6-7
Shield support for Smart Line Modules
Table 6-15
Optional shield connection plate
Designation
Article number
Tightening torque for
③
Optional shield connection plate
6SL5166-1BD00-0AA0
3 Nm (26.6 lbf in)
Accessories
6.2 Accessories for Smart Line Modules
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
97