In order to satisfy the EMC requirements, the drive system must be installed by appropriately
qualified personnel in compliance with EMC regulations and the installation notes provided in
the manual.
Note
Appropriately trained and qualified personnel
An appropriately trained and qualified person has the necessary experience for installing and/or
commissioning drive systems (Power Drive Systems - PDS), including the associated EMC
aspects.
Carefully observe the information in the "EMC installation guideline" Configuration Manual for
EMC-compliant installation.
To ensure that the drive system satisfies the requirements of the EMC category, you must comply
with the requirements listed in the subsequent table:
Table 8-2
Application conditions for S220 Smart Line Modules according to IEC 61800-3
Category
Requirements
C2
• Use radio interference suppression filters
• Operate the drive system in a network with a grounded neutral point
• Use motor cables with shielding and observe the maximum total cable lengths:
– SLM with line reactor and Basic Line Filter up to 750 m
• Ensure that the connecting cables between line filters and the Smart Line Module via
the line reactor do not exceed a total length of 10 m.
C3
• Use radio interference suppression filters
• Operate the drive system in a network with a grounded neutral point
• Use motor cables with shielding and observe the maximum total cable lengths:
– SLM with line reactor and Basic Line Filter up to 1000 m
• Ensure that the connecting cables between line filters and the Smart Line Module via
the line reactor do not exceed a total length of 10 m.
C4
The following combinations are permitted for operation in IT line systems:
• SLM with line reactor without Basic Line Filter up to 1200 m
Note
Note: Conducted interferences above 1 MHz
In individual cases, additional measures may be necessary to reduce conducted interferences
above 1 MHz. This applies particularly to the operation of Motor Modules if the settings of the
pulse frequency or the DC link voltage deviate from the default settings.
For the line supply cable, route the cores of the three individual line conductors and the cores of
the protective conductors together through the toroidal ferrite cores. Series T60006 toroidal
cores from VAC Vacuumschmelze with VITROPERM core material - for example T60006-L2080-
W531 - are recommended.
Control cabinet design and EMC booksize
8.3 Electromagnetic compatibility
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
113