4.5.3
Interface description
Overview
/ / /
①
Protective conductor
②
Load connection
③
Protective conductor
④
Line connection
You can use either the upper or lower screw to connect the protective conductor. One of the
screws remains unused. "Looping-through" the protective connection to the line reactor is not
permissible.
Line and load connections
Table 4-3
Line and load connections, Basic Line Filter for Smart Line Modules
Article number
6SL5100-
0HE21-6DD0
0HE22-4DD0
Rated power [kW]
16
24
Line connection
L1, L2, L3
Screw terminals 6 … 16 mm
2
(AWG 6 ... AWG 10), 3-pin
2.0 … 2.2 Nm (17.7 ... 19.5 lbf in)
Screw terminals 6 ... 16 mm
2
(AWG 6 ... AWG 10), 3-pin
2.0 … 2.2 Nm (17.7 ... 19.5 lbf in)
Load connection
L1´, L2´, L3´
Protective conductor connection
1)
M8 5.7 ... 6.3 Nm (55.7 lbf in)
M8 5.7 ... 6.3 Nm (55.7 lbf in)
1)
For ring cable lugs without insulation
The maximum cable length between line filter and line reactor and between line reactor and
Smart Line Module is 10 m.
Line connection and line-side power components
4.5 Line filters
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0