8.13
Power losses of the components
The tables below provide an overview of the power loss of S220 Smart Line Modules operated
at their rated power.
The total losses of the relevant power unit (Line Module, Motor Module) are calculated from the
power loss and the corresponding electronics loss of the power unit.
The following values apply under the subsequent conditions:
• Line voltage for Line Modules 400 V
• Operating components at their rated power
Table 8-21
Power losses for power units operated at their rated power (including losses of the
electronics)
S220 Smart Line Modules
Unit
Power loss
16 kW
W
150
24 kW
W
250
Table 8-22
Losses of the electronics for power units
S220 Smart Line Modules
Unit
Power loss
16 kW
W
14.9
24 kW
W
15.6
Table 8-23
Power losses at rated operation for line filters
S220 Smart Line Modules
Unit
Power loss
Basic Line Filter for Smart Line Modules
16 kW
W
12.0
24 kW
W
22.0
Table 8-24
Power losses at rated operation for line reactors
S220 Smart Line Modules
Unit
Power loss
Line reactors for Smart Line Modules
16 kW
W
90
24 kW
W
92
Control cabinet design and EMC booksize
8.13 Power losses of the components
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
143