Note
Malfunctions through magnetic fields
Line reactors produce magnetic fields that can disturb or damage components and cables.
• Arrange the components and cables at a suitable distance (at least 200 mm) or shield the
magnetic fields appropriately.
Note
Length of connecting cables
The connecting cables between line reactor and Line Module, as well as between line reactor
and line filter, must be kept as short as possible (max. 10 m).
Use shielded connecting cables and connect the cable shields at both ends.
Shielding is not required if the following preconditions are satisfied:
• The cables do not exceed 1 m in length.
• The cables are laid flush with the rear metal panel of the control cabinet.
• The cables are laid in a way that keeps them physically separate from signal cables.
All signal cables must be laid separately from the line reactor and from unshielded connecting
cables of the reactor with a minimum clearance of 200 mm.