5.11
Characteristics
Rated duty cycles S220 Smart Line Modules
Note
Maximum power, P
max
If the maximum power of the Smart Line Module is less than 300% of the rated power, then the
specified maximum power P
max
is restricted to the maximum power.
P
t
1,33 P
n
P
n
0,4 P
n
240 s
600 s
Figure 5-5
S6 duty cycle with initial load for a duty cycle duration of 600 s
t
P
300 s
1,104 P
n
60 s
P
n
0,96 P
n
Figure 5-6
Duty cycle with low overload for a duty cycle duration of 300 s
10 s
0,2 s
t
P
max
= 3 P
n
P
n
P
0,9 P
n
Figure 5-7
Peak power duty cycle with 0.2 s overload for a duty cycle duration of 10 s
Smart Line Modules
5.11 Characteristics
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
69