Table 3-4
Environmental conditions
Chemically active substances
Long-term storage
Class 1C2 according to IEC 60721-3-1:1997, in product packaging
1)
Transport
Class 2C2 according to IEC 60721-3-2:1997, in transport packaging
2)
Operation
Class 3C2 according to IEC 60721-3-3:2002
Class 3C2 according to IEC 60068-2-42
G3 according to ANSI/ISA-S71.04.2013
Class 3C3 according to IEC 60721-3-3 for H2S and SO2
Biological environmental conditions
Long-term storage
Class 1B1 according to IEC 60721-3-1:1997, in product packaging
1)
Transport
Class 2B1 according to IEC 60721-3-2:1997, in transport packaging
2)
Operation
Class 3B1 according to IEC 60721-3-3:2002
Climatic conditions
Long-term storage
Class 1K4 according to IEC 60721-3-1:1997, in product packaging
1)
Temperature: -25 … +55 °C
Transport
Class 2K4 according to IEC 60721-3-2:1997, in transport packaging
2)
Temperature: -40 … +70 °C
Operation
Class 3K3 according to IEC 60721-3-3:2002 with increased ruggedness with respect to
relative humidity
Temperature: -10 ... +40 °C without derating
> 40 ... +55 °C with a reduction of the output current by 2.5 % per °C
Relative humidity: 5 … 95 % no condensation (better than Class 3K3)
Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splash‐
ing water and water jets are not permitted
Mechanical environmental conditions
Long-term storage
Class 1M2 according to IEC 60721-3-1:1997, in product packaging
1)
Transport
Class 2M3 according to IEC 60721-3-2:1997, in transport packaging
2)
Operation
Vibration test in operation
Shock test in operation
Class 3M1 according to IEC 60721-3-3:2002
According to IEC 60068-2-6 test Fc (sinusoidal)
• 10 ... 57 Hz: 0.075 mm deflection amplitude
• 57 ... 150 Hz: 1 g acceleration amplitude
• 10 frequency cycles per axis
According to IEC 60068-2-27 test Ea (half-sine)
• 5 g peak acceleration
• 30 ms duration
• 3 shocks in all three axes in both directions
System overview
3.4 S220 components and system data
Booksize power units
34
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0