Technical data
8.1 Technical data
Equipment Manual, 09/2022, L1V30415168B-03
79
Measuring accuracy
Applicable standards:
•
IEC 61557-12
•
IEC 62053-22
•
IEC 62053-23
Measured variable
Accuracy class
Voltage
0.5 (IEC 61557-12)
Current
0.5 (IEC 61557-12)
Neutral conductor current (calculated)
1 (IEC 61557-12)
Total apparent power
0.5 (IEC 61557-12)
Total active power
0.5 (IEC 61557-12)
Total apparent power
0.5 (IEC 61557-12)
Total reactive power
2 (IEC 61557-12)
Total power factor
0.5 (IEC 61557-12)
Line frequency
0.05 (IEC 61557-12)
Total active energy
0.5 (IEC 61557-12)
Total reactive energy
2 (IEC 61557-12)
Total active energy
0.5 (IEC 62053-22)
Total reactive energy
2 (IEC 62053-22)
When measuring on external current transformers or voltage transformers, the accuracy of
the measurement depends on the quality of the transformer.
Power supply
Power supply
Design of the power supply
Wide range AC / DC power supply
Work area
110 V - 250 V ±10%
Power consumption
5 VA
Overvoltage category
OVC
Digital Input
Digital Input
Number
1
Type
Passive
Maximum switching voltage
30 V
Input current
"1" signal detection
2.5 … 10 mA
"0" signal detection
≤0.5
mA
Содержание SENTRON PAC3200T
Страница 1: ......
Страница 2: ......
Страница 8: ......
Страница 14: ......
Страница 30: ......
Страница 46: ......
Страница 54: ......
Страница 74: ......
Страница 88: ......
Страница 89: ...Equipment Manual 09 2022 L1V30415168B 03 87 Dimensional drawings 9 Frame dimensions ...
Страница 90: ......
Страница 134: ...Equipment Manual 09 2022 L1V30415168B 03 132 ...
Страница 135: ......
Страница 136: ......