Appendix
A.1 Modbus TCP
120
Equipment Manual, 09/2022, L1V30415168B-03
A.1.8
Structure - Device diagnostics and device status with the function codes
0x03 and 0x04
Structure
Table A- 5
Modbus offset 205, register 2: Structure device status and device diagnostics
Byte Bit
Device status
Type
Bit mask
Value range Access
0
0
No synchronization pulse
Status
0x01000000
0 =
not active
1 =
active
R
0
1
Device configuration menu is active
Status
0x02000000
R
0
2
Voltage overload
Status
0x04000000
R
0
3
Current overload
Status
0x08000000
R
0
5
Update status is active
Status
0x20000000
R
0
6
Hardware write protection is active
Status
0x40000000
R
0
7
Modbus communication is write-protected Status
0x80000000
R
1
1
Maximum pulse rate exceeded
Status
0x00020000
R
2
0
Relevant parameter changes
1)
Saving
0x00000100
R
2
2
Maximum pulse rate exceeded
1)
Saving
0x00000400
R
2
3
Restart of the device
1)
Saving
0x00000800
R
2
4
Resetting of energy counter by user
1)
Saving
0x00001000
R
1) Only these device statuses are to be acknowledged.
Содержание SENTRON PAC3200T
Страница 1: ......
Страница 2: ......
Страница 8: ......
Страница 14: ......
Страница 30: ......
Страница 46: ......
Страница 54: ......
Страница 74: ......
Страница 88: ......
Страница 89: ...Equipment Manual 09 2022 L1V30415168B 03 87 Dimensional drawings 9 Frame dimensions ...
Страница 90: ......
Страница 134: ...Equipment Manual 09 2022 L1V30415168B 03 132 ...
Страница 135: ......
Страница 136: ......