Commissioning
6.3 Parameterizing the device
Equipment Manual, 09/2022, L1V30415168B-03
57
6.3.1.4
Setting basic parameters
Basic parameters are all those settings concerning the measuring inputs.
"Connection type" parameter
The "Connection type" parameter limits the total number of measured variables. The input
circuit of the device must correspond to the parameterized connection type.
Inform the device of the connection type used by entering the connection type code in the
device settings.
Selection
Range
Factory
setting
Connection
type
•
3P4W:
3 phases, 4 conductors, unbalanced load
3P4W
•
3P3W:
3 phases, 3 conductors, unbalanced load
•
3P4WB:
3 phases, 4 conductors, balanced load
•
3P3WB:
3 phases, 3 conductors, balanced load
•
1P2W:
1 phase, 2 conductors, unbalanced load