6 Clip-in function module AGU2.51x
07.11.2002
The function of the input on the clip-in function module is defined via parameter
«KonfigEingangR».
Since the function of the input depends on the version of the clip-in function module, it is
checked first whether the parameterized function can be performed by the connected
module version.
If that is not the case, an error message will be delivered.
The input of the clip-in function module is used by the LMU… as another programmable
input (
→
Programmable input of the LMU...).
The LP contact
can never
be read in via the input of the clip-in function module!
The following functions can be selected via parameter «KonfigEingangR»:
•
4 Predefined setpoint
•
5 Predefined output
•
6 Sensor input “Pressureless header”
In that case, the heat demand (temperature demand) is predefined via an analog signal.
This can take place via a current signal (4...20 mA) or voltage signal (DC 0...10 V).
The maximum value is defined via parameter «TanfoExtMax » on the LMU... The setting
range of this parameter is from 5 to 130 °C, the resolution being 1 °C.
The heat demand is derived from the the temperature demand.
For that, the threshold value is 5 °C. If the temperature demand is > (5+1) °C, the heat
demand will be set. If the temperature demand is < (5-1) °C, the heat demand will be
reset.
Both temperature and heat demand are assigned to heating circuit 1 of the LMU... .
Any additional heat demand that might exist at the same time will be accepted. The
temperature demand is determined via the maximum value.
U (V)
5
S = 5 °C!
I (mA)
20
130 Temp. (°C)
7494d42/0702
10
8
6
4
2
0
0
Parameter «TAnfoExtMax»
16
12
8
4
Predefined setpoint
Inputs
Digital input
Note
Analog input
Predefined setpoint
(temperature demand)