Below, the full functionality of the LMU... is described. For information on the scope of
functions of a specific unit, refer to the relevant version / configuration.
•
Gas burner control conforming to EN 298 for intermittent operation
•
Integrated boiler / burner control for space heating and DHW operation
•
Sequence control depending on the boiler’s capacity: < 70 kW, 70 - 120 kW, or > 120 kW.
Boiler capacities up to about 600 kW can be handled (depending on the type of fan /
gas valve used)
•
Integrated electronic (safety) limit thermostat
•
Integrated limit thermostat function
•
Direct ignition of the main flame by means of
−
integrated single-pole high-voltage ignition (with the choice of single-electrode
operation)
−
external AC 230 V ignition control (optional)
•
Continuous (analog) ionization current supervision with optional indication of flame
intensity
•
Gas valve control AC 230 V (RAC optional)
•
Number of start repetitions can be programmed
•
Quick startup (especially in connection with instantaneous DHW systems)
•
Fan supervision
•
Optimization of combustion (optional)
•
Control of an AC 230 V fan (DC 24 V fan optional)
•
Ignition load precontrol via speed readjustment
•
Adaptive postpurge level of fan speed
•
Load limitation (fan limitation by minimum / maximum speed and / or flame signal)
•
Number of fan feedback pulses can be selected
•
Flame stabilization time
•
Boiler cycling protection via minimum boiler off time
•
Dynamic switch-off differentials for space heating (Hz) and DHW (Bw) operation
•
Pump and diverting valve kick
•
Frost protection functions for the plant, the boiler, DHW and the room
•
Water pressure supervision (pressure sensor with static and / or dynamic supervision,
contact for pressure switch, flow switch)
•
Flue gas temperature supervision
•
OCI420
clip-in for communication, LPB interface for ALBATROS system world
•
AGU2.500
clip-in for additional heating circuit
•
AGU2.51x
clip-in function module
- inputs:
NTC, 10 k
Ω
digital input
0(4)...20 mA
DC 0...10 V
- outputs:
max. 3 relays AC 230 V
Safety functions
Supervision / protective
functions for the plant
Auxiliary modules
(clip-in)