140/171
Siemens Building Technologies
Basic Documentation LMU54... / LMU64...
CC1P7494en
HVAC Products
12 Parameter list / legend of parameter bit fields LMU...
07.11.2002
No
Name
Group
Function
Range
No
QAA73
AGU2.310
Level
QAA73
AGU2.310
LevelNo
PC_Tool
Level
PC_Tool
Production data and version
289 KundeNr
INFO values
Official L & S customer number
0 ... 255
1
L&S service
(Development)
5
ParaVersNr
INFO values
Parameter set version number
0 ... 65535
1
L&S service
(Development)
6
ParaSatzNr
INFO values
Parameter set number
0 ... 65535
1
L&S service
(Development)
527 P_Kenn
Parameterization
Identification of parameter set. PC tool programmed
from OEM level only when this parameter is identical
0 ... 255
2
L&S temp
7
FabJahr
INFO values
Production year
0 ... 255
0
L&S production
8
FabMonat
INFO values
Production month
0 ... 255
0
L&S production
9
FabTag
INFO values
Production day
0 ... 255
0
L&S production
1 0 FabNr
INFO values
Production number
0 ... 2147483647
0
L&S production
1 1 Pruefer
INFO values
Inspector code
0 ... 255
0
L&S production
348 GerFam
INFO values
Device family
0 ... 255
5
Installer
Operating data, learn adaption range
6 8 BetrStd
INFO values
Hours run burner
0 ... 131070 hrs
718
Engineer*
1
L&S service
(Development)
6 9 BetrStdHz
INFO values
Hours run heating mode
0 ... 131070 hrs
719
Engineer*
1
L&S service
(Development)
7 0 BetrStdBw
INFO values
Hours run DHW heating
0 ... 131070 hrs
720
Engineer*
1
L&S service
(Development)
7 1 BetrStdZone
INFO values
Hours run zone
0 ... 131070 hrs
721
Engineer*
1
L&S service
(Development)
7 2 InbetrSetz
INFO values
Start counter
0 ... 327675
722
Engineer*
1
L&S service
(Development)
246 TvSollMmiEeprom
INFO values
Initialization value of boiler setpoint potentiometer
20 ... 90 °C
1
L&S service
(Development)
511 TvSollRedMmiEeprom
Initialization
Initialization value of boiler setpoint potentiometer
reduced
5 ... 90 °C
1
L&S service
(Development)
247 TrSollMmiEeprom
INFO values
Initialization value of room setpoint potentiometer
10 ... 30 °C
1
L&S service
(Development)
512 TrSollRedMmiEeprom
Initialization
Initialization value of room setpoint potentiometer
reduced
10 ... 30 °C
1
L&S service
(Development)
248 TbwSollMmiEeprom
INFO values
Initialization value of DHW setpoint potentiometer
10 ... 80 °C
1
L&S service
(Development)
513 TbwSollRedMmiEeprom
Initialization
Initialization of DHW setpoint potentiometer reduced
10 ... 80 °C
1
L&S service
(Development)
7 4 MmiStatus
HMI
Selection of summer / winter operating modes
0 ... 255
724
Engineer*
1
L&S service
(Development)
7 3 Pmittel
No meaning
Mean boiler output
-
723
Engineer*
-
-
474 SwVersion_LMU
INFO values
SW version of LMU for presentation on the OT
parameter setting level
-
725
Engineer*
-
-
240 IonStrom
INFO values
Measured value of ionization current
-
755
Engineer*
-
-
*
Read only
Mixing valve clip-in
441 XpHz2
Heating mode AGU2.500
P-band of heating circuit 2 controller
1 ... 100 K
597
OEM
4
OEM service
166 TnHz2
Heating mode AGU2.500
Integral action time of heating circuit 2 controller
10 ... 873 s
574
OEM
4
OEM service
442 ZeitAufZu
Heating mode AGU2.500
Running time of actuator in heating circuit 2
(TimeOpening / TimeClosing)
30 ... 873 s
596
Engineer
4
OEM service
443 SdHz2
Heating mode AGU2.500
Switching differential of 3-position controller in heating
circuit 2 (<= neutral zone (2K))
0 ... 2 K
4
OEM service
445 KoeffSperr
Heating mode AGU2.500
Weighting factor for locking signal in heating circuit 2
0 ... 200 %
1
L&S service
(Development)
LPB clip-in
1 7 LPBKonfig0
Boiler OCI420
Setting flags for time synchronization and power supply
on LPB
0 ... 255
604
Engineer
5
Installer
380 LPBAdrSegNr
Boiler OCI420
LPB segment number of LMU
0 ... 14
606
Engineer
5
Installer
381 LPBAdrGerNr
Boiler OCI420
LPB device number of LMU
0 ... 16
605
Engineer
5
Installer
416 LPBGeraeteVariante
Boiler OCI420
Device variant within the LMU6x family
0 ... 255
1
L&S service
(Development)
415 LPBErrorGerAlarm
Boiler OCI420
Setting flags for configuring the device alarm on LPB
0 ... 255
1
L&S service
(Development)
Burner control identification
Operating data
MCI
LPB