The 2-position controller generates the signal for startup or shutdown by the burner
control:
Startup = «On» at
TkIst < TkSoll - SdEin
Shutdown = «Off» at
TkIst > SdAus
The switching differentials will be loaded depending on the compensation variant. Also,
the dynamic switch-off differential has an impact on the value of «SdAus ».
The minimum boiler pause time locks the boiler for an adjustable period of time
«ZBreMinP».
This time commences after normal shutdowns or when the temperature limiter responds
in the case of heat demand, but the 2-position controller initiates a new startup only
when this period of time has elapsed.
•
Release of minimum pause time:
After the flame signal is safely detected, the minimum pause time will be released, that
is, the pause time can be started by the 2-position controller with the next shutdown.
•
Start of minimum pause time:
After release of the minimum pause time on shutdown by the 2-position controller or
temperature limiter, the timer will be loaded with the time «ZBreMinP» and then started.
•
Interruption of minimum pause time:
If, during the minimum pause time, one of the following functions is called for, it will
immediately be started. In the background, the minimum pause time for the heating
circuit continues to run.
−
DHW demand
−
Frost protection for the boiler
−
Controller stop function
−
Chimney sweep function
If the demand is terminated during that period of time, the demand for heating will
continue to be locked until the minimum pause time has elapsed.
•
Termination of minimum pause time:
−
On completion of the minimum pause time
−
When there is no more demand for heating (Hz1, Hz2 or HzZone)
−
When a maximum control differential
∆
T = «TkSoll – TkIst» is exceeded
If, during the boiler’s minimum pause time, the boiler temperature drops excessively, the
pause time will be terminated when a maximum control differential is reached and
startup will be released again.
∆
T
≥
dTbreMinP
The minimum pause time will be restarted with the next shutdown.
Boiler cycling protection is accomplished with different methods, depending on the
operating mode.
Heating
mode
DHW storage tank
Instantaneous
DHW heater
1)
Dynamic switch-off differential
X
X
X
Minimum boiler pause
X
1)
= outlet temperature control
Boiler temperature control
2-position control
Minimum boiler
pause time
Boiler cycling protection