Basic Documentation LMU54... / LMU64...
CC1P7494en
HVAC Products
12 Parameter list / legend of parameter bit fields LMU...
07.11.2002
12.3 Legend of parameter bit fields LMU...
KonfigRg0
Setting flags:
Status code open-circuit sensor channel Anx
suppressed / not suppressed
MeldAN2
Status code open-circuit sensor channel AN2
XXXX XXX0
suppress
XXXX XXX1
deliver
MeldAN3
Status code open-circuit sensor channel AN3
XXXX XX0X
suppress
XXXX XX1X
deliver
MeldAN4
Status code open-circuit sensor channel AN4
XXXX X0XX
suppress
XXXX X1XX
deliver
MeldAN5
Status code open-circuit sensor channel AN5
XXXX 0XXX
suppress
XXXX 1XXX
deliver
MeldAN6
Status code open-circuit sensor channel AN6
XXX0 XXXX
suppress
XXX1 XXXX
deliver
MeldVLHz2
Status code open-circuit flow sensor HC2
XX1X XXXX
deliver
MeldFueRelCl
Status code open-circuit sensor on clip-in function module
X0 XX XXXX
suppress
X1 XX XXXX
deliver
KonfigRg1
Setting flags
BwVor
DHW priority
XXXX XX00
absolute
XXXX XX10
no priority
Schaltuhr1
Terminal assignment RT (X10-02; can also act on heating
circuit 2, if RU is connected)
XXXX X0XX
RT
XXXX X1XX
time switch
Schaltuhr2
Terminal assignment OT (X10-01; if RU is connected,
terminal RT can also act on heating circuit 2->time switch)
XXXX 0XXX
RT
XXXX 1XXX
time switch
AnlagenFrost
Frost protection for the plant
XXX0 XXXX
OFF
XXX1 XXXX
ON
Schaltuhr2Bw
Assignment of second time switch to OT terminals
(X10-01)
XX0X XXXX
time switch acts on HC
XX1X XXXX
time switch acts on DHW
Controller functions