Siemens Building Technologies
Basic Documentation LMU54... / LMU64...
CC1P7494en
HVAC Products
4 Clip-in AGU2.500... for additional heating circuit
07.11.2002
4
Clip-in AGU2.500... for additional
heating circuit
The description below covers the full functionality of the AGU2.500... system.
For the concrete scope of functions, refer to the relevant version / configuration.
•
Additional pump or mixing circuit for single-user applications
•
Independent heating circuit with own
−
time switch program
−
heating curve
−
minimum / maximum limitation of the flow temperature
•
Central operation of the 2 heating circuits via the QAA73...
•
Straightforward attachment of clip-in module AGU2.500... to the housing of the
LMU6...
•
RAST5 connectors for all inputs and outputs
Maximum one clip-in module AGU2.500... can be connected to the LMU5... / LMU6... .
A maximum of 2 clip-in modules (OCI420 / AGU2.500... / AGU2.51x) can be connected.
On the LMU..., the respective hydraulic diagrams
must
be activated via parameter
«HydrSystem»:
•
Pump circuit extensions:
Diagrams 32 ... 47
•
Mixing circuit extensions:
Diagrams 48 ... 63
•
Zone extensions:
Diagrams 64 ... 79
With certain hydraulic diagrams using the AGU2.500... applications, an additional
actuating device Y1 (programmable output K2 of the LMU...) in the LMU… pump circuit
is used to ensure overtemperature protection.
•
Flow sensor
The sensor used has a sensing element NTC 10 k
Ω
. Its characteristic is the same as
that of the NTC sensor read in by the LMU… basic unit.
Temperature
Measuring range
Read-in range
Tolerance
Resolution
Flow temperature
0...100 °C
-5...125 °C
±
3 K
0.3 K
The read-in tolerance is the worst-case device accuracy excluding the sensor tolerance.
Refer to «Connection diagrams».
Functions
General
Note
Hydraulic diagrams
Note
Sensor inputs
(analog inputs)
Note
Inputs / outputs